COMMON MESSAGES

Door Window Sensor User Guide

15

Radio Config

The following table shows the radio config byte definition.

Note:

Available in firmware version 1.4 or newer.

Bits

Description

7

Not used (reserved)

6

Enable duty cycle requirement.

LoRaWAN EU868 only

. To enforce the EU868 band duty cycle

requirements, enable before production deployment. Default is disabled. Available in firmware
2.2.1 or later.

5:2

Uplink retries.

LoRaWAN only

. The range for uplink retries is 1-8 for confirmed messages (ACK

required) and does not apply to unconfirmed messages. Default 0 (leave unchanged). Available in
firmware v1.4 and above.

1

Use unconfirmed messages.

LoRaWAN only

. If set to use the unconfirmed messages bit, the sensor

does not look for an ACK from the network server. Default is 1 (unconfirmed messages, no ACK
required). EU sensors can’t use confirmed messages, setting this bit to 0 on an EU device causes an
error. Available in firmware v1.4 and above.

0

Disable Adaptive Data Rate (ADR).

LoRaWAN only

. To enable ADR, set to 0. To disable ADR, set to

1. Default is 0 (enabled). Available in firmware v1.3 and above.

Important:

The duty cycle bit must be set for production deployments in the EU868 band.

Supervisory Period

The general configuration command’s supervisory period controls the time between supervisory messages as
defined in the following table.

Bit 7

Bits 6:0

0

Period defined in hours (1-127 hours). Available in firmware v1.3 and above.

1

Period defined in minutes (1-127 minutes) Available in firmware v1.3 and above.

For example, to receive a report every 4 hours, set Byte 1 to 0x04. To receive a periodic report every 15 minutes,
set Byte 1 to 0x8f.

Sampling Rate

Sampling rate controls the frequency at which devices wake from low power sleep mode to check the sensor state.
Some sensors require very little power to check the state and need to react quickly. Other sensors can be sampled
at a lower rate, such 30-second or 30-minute intervals. Increasing the time between samples increases battery life.

Refer to the Battery Estimator on the Radio Bridge site for battery life estimates relative to sampling rate:

https://radiobridge.com/documents/Sensor%20Battery%20Estimator.xlsx

A value of 0 in this field leaves the sampling rate at the current value. Use the following table to determine the
sampling rate if the value is not zero.

Note:

Sampling period only applies to sensors that take measurements like temperature and tilt, it does not

apply to sensors with binary inputs such as door/window sensors or push buttons.

This feature is available in firmware v2.0 and above.

Содержание REVEAL RBS301-DWS

Страница 1: ...Door Window Sensor User Guide...

Страница 2: ...change without notice and does not represent a commitment on the part of Multi Tech Systems Inc Multi Tech Systems Inc provides this document as is without warranty of any kind expressed or implied in...

Страница 3: ...Sensors 9 Armored Outdoor Industrial RBSx06 Sensors 10 Chapter 4 Common Messages 11 Common Messages 11 Message Protocol 11 Uplink Messages 11 Reset Message 0x00 12 Supervisory Message 0x01 13 Tamper M...

Страница 4: ...RaWAN Europe RBS301 DWS AU Indoor LoRaWAN Australia South America RBS306 DWS US Outdoor Industrial LoRaWAN North America South America RBS306 DWS EU Outdoor Industrial LoRaWAN Europe Documentation The...

Страница 5: ...ve a tab that does not pull out easily Loosen screws to remove the battery tab DO NOT REMOVE THE LID Hand tighten the lid screws to seal the case against moisture Do not overtighten the screws Quick S...

Страница 6: ...le shows complete when the device is successfully added Mounting the Sensor The window door sensor includes a sensor and a magnet that need line up 1 Use the included large adhesive pad to secure the...

Страница 7: ...ARING SENSOR Door Window Sensor User Guide 7 The tab will break away and send a tamper alert if the case is forcibly removed 5 Attach the magnet piece to the door so it aligns with the natch on the se...

Страница 8: ...t for high power radio technologies e g LoRaWAN Different battery types deplete over time with different voltage profiles a lithium battery maintains high voltage for the life of the battery with a ra...

Страница 9: ...NS AND INFORMATION Door Window Sensor User Guide 9 Mechanical Drawings The mechanical drawings provided in this section are for the main body of the sensor All dimensions use inches unless specified I...

Страница 10: ...HARDWARE SPECIFICATIONS AND INFORMATION 10 Door Window Sensor User Guide Armored Outdoor Industrial RBSx06 Sensors...

Страница 11: ...the specific format of a message type Packet Count 4 bits A sequential number starting at 0 for the first message sent from the sensor to the cloud It increments by one for each subsequent message Wh...

Страница 12: ...entifier sent as part of the reset message Door Window 0x01 1 Hardware version 2 3 Firmware version 4 5 Reset code Used for factory diagnostics Firmware Version The 16 bit firmware version is construc...

Страница 13: ...level is a two digit battery voltage For example if the battery voltage is 2 9V byte 2 would be 0x29 3 6 Extended sensor state 4 bytes Allows sensors with higher precision or multiple values to repor...

Страница 14: ...since the sensor is typically sleeping with the radio turned off For LoRaWAN devices a downlink can be received after any uplink within the receive window The following messages can be sent back to th...

Страница 15: ...Supervisory Period The general configuration command s supervisory period controls the time between supervisory messages as defined in the following table Bit 7 Bits 6 0 0 Period defined in hours 1 12...

Страница 16: ...aWAN only Port Number For LoRAWAN devices only Byte 0x01 of the advanced configuration command changes the uplink port per the LoRaWAN protocol The default port is 2 and a value of 0 in this field mea...

Страница 17: ...e to verify the that sensor received the downlink message received and it was considered valid The sensor replies to the downlink data with a 0xFF message downlink ACK with the payload shown in the fo...

Страница 18: ...a particular position open or closed before a message is sent An example of how this is would be used when monitoring a door to a refrigeration unit When the door is open or shut with say 1 minute no...

Страница 19: ...sensors FCC ID 2APNUCMABZ LoRaWAN RBS306 sensors This device contains FCC IAU792U13A16858 This device contains equipment certified under IC 125A 0055 Harmonized Commodity Description HS Code The Harm...

Отзывы: