background image

Dimension

90.00 

47.00 

22.5

66.35

NOTE:
All dimension are in mm.

L1-L2

L2-L3

L3-L1

T

ON  

ON  

P

15

18

16

T

T

Phase
  Loss

ON  

ON  

Control Function

< 280V AC (L-L)

Phase Loss

 40V AC (L-L)

Phase Asymmetry

6 V

Hysteresis

= Power ON Delay (5 sec)

Over Voltage

Under Voltage

Hysteresis

Hysteresis

T

P

T

= Trip Delay (5 sec)

Terminal Connection

L1

L3

16

15 18

L2

Output : 

1 Relay 1C/O , 
5A, 230V AC (Res.)

Input Voltage:

 

280 to 520V AC (L-L)
3Ø - 3W

Function : 

Phase Loss < 280V AC (L - L)
Phase Asymmetry > 40V Fix
Hysteresis : 6V Fix
Rated Voltage: 415V AC (L-L)

-

Self Powered

NO 

C

NC 

18

15

16

Power Supply :

Delay Time :

Trip Delay: 15/10/5/0 Sec Selectable
Power ON Delay: 15/10/5/0 Sec Selectable
PS,PL: <200ms
Asymmetry: 5 Sec.

-

LED Indication:

 

RED: PL
Blinking Red: PA
Yellow: PS
OFF: Healthy