Installation and Setup
Section 4: Installation and Setup
Installing and wiring the Safety Automatic Transfer Switch into an enclosure may be accomplished by con-
necting the utility AC input wires and cabinet load wires to the appropriate connectors of the SATS. If in use,
the generator wires from the outside generator cabinet connector may also be wired to the appropriate
connector. The UPS power harness shall be used to connect the SATS to the UPS according to the wiring dia-
gram. The 7-position dry contact relay connector may be wired to sense the presence of power and report
this to a conflict monitor when MAINS or GEN power is currently active or inactive.
In all installations, the following conditions apply and must be observed:
• A service disconnect switch containing over-current protection devices such as circuit breakers or
fuses with appropriate AIC (amperes – interrupting capacity) rating should be placed between the
AC utility source and the service entrance device for the SATS. Where used, the disconnect switch
must be installed in compliance with all national, state and local codes as required.
• For outdoor installations, the AC utility conductors connected to the cabinet service entrance de-
vice shall be physically protected through an appropriate restraining device and conduit, consistent
with local codes and practices.
• Permission to mount the SATS enclosure at any site shall be made in accordance with all legal re-
quirements and local practices of the area.
This SATS is designed for use in both existing and new ground-mount enclosures. Observe the following
procedures during installation of any SATS.
Preparation
The Safety Automatic Transfer Switch has been factory assembled, tested and prepared as a complete
product ready for installation within an enclosure. The installer must verify that the correct type of AC
power receptacle is installed in the enclosure for the input service and SATS selected for use at any giv-
en site. SATS ratings may be verified from the nameplate on the top of the SATS near the duplex outlet.
Grounding
Safety ground and earth ground connections must be in place for the SATS and enclosure for both per-
sonal safety and operational considerations. During SATS and/or enclosure installation, the following
grounding connections must be provided or verified.