The Multicalor MC-EE (modulating) air handling units are 
compact high performance units. The units are fitted with ge-
nerously sized heat exchangers featuring 6 rows. This guaran-
tees high air temperatures even with moderate supply water 
temperatures. As a result, the units are very well suited to be 
used in conjunction with modern condensing boilers. 

The fans of the MC units are installed downstream of the heat 
exchangers. This ensures that the fan motors are always opti-
mally cooled and the life span of the fan bearings is increased. 
Special attention has been paid to the air tightness of the 
units, so leak losses are minimal. The heat exchanger com-
partments is insulated by means of a thick layer of air, so heat 
losses are minimal. The apparatus is supplied ready to use. It 
is sufficient to install on site the hot water supply lines, the air 
ducts and the electrical supply.

The MC-EE is fitted with an advanced controller based on an 
Atmel RISC microcontroller and a high performance and high 
efficiency electronically controlled fan motor.

In standard use the apparatus is used to distribute recycled air 
to which not more than 25% outside air has been added, or to 
distribute up to 100% outside air after heat reclaim. The unit is 
factory supplied in this version.

In outside air version the unit is used to distribute air to which 

more than 25% outside air is added. You can activate a special  
program in the controller as to maintain a minimum air tem-
perature (for best results an optional modulating 3-way valve 
should be connnected). When this option is activated, a basic 
frost-protection is activated to help protect the heat exchan-
ger in case of frost danger. Nevertheless we suggest adding a 
suitable anti-freeze solution to the heating circuit if the unit is 
used as an outside air version.

The Multicalor MC units are available as upflow models. If you 
need a downflow unit, you can turn simply around the unit  
and flip the controller panel. Pay attention as to not drop the 
panel – this may damage the flatcable connector. 

1 General

2  Technical data

2.1 General

The units comply to the machine directive 89/392/EEG, the 

low voltage directive 73/23/EEG and the EMC directive 

89/336/EEG. 

The MC units are available in 3 sizes. Each unit is fitted with 

an electronically commutated fan. You can easily change 

the maximum airflow by reprogramming the unit via the 

touscreen.

Unit

MC-EE 20

MC-EE 30

MC-EE 40

Fan data

Type

9/7

10/8

10/10

Motor power

Watt

376

550

736

Air flow (min-max)

m³/h

1 500

2 250

3 000

Opgenomen vermogen (80% speed)

A

1.40

1.90

2.20

Hydraulic pressure drop

kPa

3.51

3.81

4.61

Heating output (75/65-20°C (EN442)) 

kW

20.0

30.0

40.0

Waterdebiet

l/s

0.5

0.74

0.98

Weight

kg

68

78

88

2.2 

Prestaties van de toestellen

2.3 

Correction factors for other hot water supply- or entering air temperatures

Hot water supply

Air temperature entering the unit

30

25

20

18

15

10

90/70

99%

109%

119%

123%

129%

138%

75/65

81%

90%

100%

104%

110%

119%

70/50

52%

63%

74%

78%

84%

94%

60/50

48%

58%

68%

72%

78%

88%

45/40

23%

34%

44%

48%

54%

64%

Содержание MC-EE 20

Страница 1: ...Cooling Ventilating MC EE Manual Air handlers featuring an advanced electronic modulating controller and electronically commutates high efficiency fan motor electronically enhanced MC EE 20 MC EE 30 M...

Страница 2: ...on site 8 3 2 Electrical installation 8 3 2 1 Electrical connections 8 3 2 2 Thermostat 8 4 3 3 Advanced options 9 4 4 Installing the hot water supply lines 9 4 4 1 Hydraulic installation simple versi...

Страница 3: ...t IV_MCEE_2016_11_22 3 Dimensions A B 720 00 1 1 00 0 0 550 00 673 00 8 00 0 0 3 66 0 0 470 00 500 00 91 1 00 40 6 00 D C 600 00 Type A B C D MC 20 340 400 280 220 MC 30 440 500 380 320 MC 40 540 600...

Страница 4: ...an activate a special program in the controller as to maintain a minimum air tem perature for best results an optional modulating 3 way valve should be connnected When this option is activated a basic...

Страница 5: ...3 21 33 45 1 2 3 4 5 6 7 Legend Number Meaning 1 Function mode of the appliance 2 Air temperature 3 Time 4 Fan speed 5 Information menu button 6 Settings menu button 7 Date 3 2 2 Locking If an error o...

Страница 6: ...as last the air flow rate Low speed at Medium speed at High speed at Fan curve CH 1 50 10 80 Laag Midden Hoog 1 2 3 4 9 5 6 Next select the value that you want to change The selected value for example...

Страница 7: ...e screen using a microfibre cloth or with a paper tissue 3 3 7 Installer s menu Specific parameters can be found on an installer s menu to stop thoughtless changes This installer s menu can only be ac...

Страница 8: ...50 mm clearance around the sides of the unit keep a minimum of 50 mm between hot water supply and any flammables At the front of the device there shall be at least 720 mm of free service space ensure...

Страница 9: ...us for more information 4 3 3 5 Extension board It s possible to connext an extension PCB board to achieve multiple zone control For more information contact the manufacturer 4 4 Installing the hot w...

Страница 10: ...eed as follows to switch the machine ON Connect the mains power Set the room thermostat at the desired setting Proceed as follows to switch the machine OFF Set the room thermostat 5 C lower than the a...

Страница 11: ...n extent that the machine may incur irretrievable damage which the warranty does not cover 5 1 2 Cleaning the casing The casing may be cleaned with a soft humid cloth Do not use aggressive media such...

Страница 12: ...rint 0DA_MC NTC2 NTC2 NTC1 A NTC1 B GND V12 FAN J7 L N PE C Rx Tx V FAN THERMOSTAT W G R MC EE UF DF DISP J6 Print 0D1 Flat Cable 2016 11 22 Heat I1 Ventilation I3 NO COM NO COM NO COM NC Return Air S...

Страница 13: ...s The heat exchanger when used in an atmosphere polluted with chlorine or other chemicals Causes foreign to the machine including but not restric ted to 1 Damage incurred during transport including de...

Страница 14: ...icalor Industries declares that the air handlers Multicalor MC 20 Multicalor MC 30 Multicalor MC 40 meet the provisions of the machine directive 89 392 EEC the low voltage directive 73 23 EEC as well...

Страница 15: ...Document IV_MCEE_2016_11_22 Modificationsreserved 15...

Страница 16: ...Industries NV Blarenberglaan 21 B 2800 Mechelen Belgium www multicalor be Tel 32 15 29 03 03 Fax 32 15 29 03 20 info multicalor be For more information contact your installer Last modification 22 nov...

Отзывы: