4
Modifications reserved
Document: IV_MCEE_2016_11_22
The Multicalor MC-EE (modulating) air handling units are
compact high performance units. The units are fitted with ge-
nerously sized heat exchangers featuring 6 rows. This guaran-
tees high air temperatures even with moderate supply water
temperatures. As a result, the units are very well suited to be
used in conjunction with modern condensing boilers.
The fans of the MC units are installed downstream of the heat
exchangers. This ensures that the fan motors are always opti-
mally cooled and the life span of the fan bearings is increased.
Special attention has been paid to the air tightness of the
units, so leak losses are minimal. The heat exchanger com-
partments is insulated by means of a thick layer of air, so heat
losses are minimal. The apparatus is supplied ready to use. It
is sufficient to install on site the hot water supply lines, the air
ducts and the electrical supply.
The MC-EE is fitted with an advanced controller based on an
Atmel RISC microcontroller and a high performance and high
efficiency electronically controlled fan motor.
In standard use the apparatus is used to distribute recycled air
to which not more than 25% outside air has been added, or to
distribute up to 100% outside air after heat reclaim. The unit is
factory supplied in this version.
In outside air version the unit is used to distribute air to which
more than 25% outside air is added. You can activate a special
program in the controller as to maintain a minimum air tem-
perature (for best results an optional modulating 3-way valve
should be connnected). When this option is activated, a basic
frost-protection is activated to help protect the heat exchan-
ger in case of frost danger. Nevertheless we suggest adding a
suitable anti-freeze solution to the heating circuit if the unit is
used as an outside air version.
The Multicalor MC units are available as upflow models. If you
need a downflow unit, you can turn simply around the unit
and flip the controller panel. Pay attention as to not drop the
panel – this may damage the flatcable connector.
1 General
2 Technical data
2.1 General
The units comply to the machine directive 89/392/EEG, the
low voltage directive 73/23/EEG and the EMC directive
89/336/EEG.
The MC units are available in 3 sizes. Each unit is fitted with
an electronically commutated fan. You can easily change
the maximum airflow by reprogramming the unit via the
touscreen.
Unit
MC-EE 20
MC-EE 30
MC-EE 40
Fan data
Type
9/7
10/8
10/10
Motor power
Watt
376
550
736
Air flow (min-max)
m³/h
1 500
2 250
3 000
Opgenomen vermogen (80% speed)
A
1.40
1.90
2.20
Hydraulic pressure drop
kPa
3.51
3.81
4.61
Heating output (75/65-20°C (EN442))
kW
20.0
30.0
40.0
Waterdebiet
l/s
0.5
0.74
0.98
Weight
kg
68
78
88
2.2
Prestaties van de toestellen
2.3
Correction factors for other hot water supply- or entering air temperatures
Hot water supply
Air temperature entering the unit
30
25
20
18
15
10
90/70
99%
109%
119%
123%
129%
138%
75/65
81%
90%
100%
104%
110%
119%
70/50
52%
63%
74%
78%
84%
94%
60/50
48%
58%
68%
72%
78%
88%
45/40
23%
34%
44%
48%
54%
64%