background image

 

                                                        

 

 

 

INSTALLATION & OPERATING 

MANUAL 

MHCCW Fan Coils 1- 3 Tons 

 

ENCLOSURE 

FAN 

COIL 

ENCLOSURE  DIMENSIONS (in.) 

PART NUMBER 

SIZE 

Depth    Length  Height  Weight (LBS.) 

MPE468 

32.75  39.75  11.00 

26 

MPE468 

32.75  39.75  11.00 

26 

MPE468 

 32.75 

39.75  11.00 

26 

MPE10 

10 

 32.75 

45.75  11.00 

30 

MPE12 

12 

 32.75 

51.75  11.00 

34 

                                               Figure 2 

          

 

 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
                  
 
 
 
 
 
 
   

 

 

 

 
 
 
 
 
                                                               

 

                                                                                   
 
 
           
 

 

                                                                                           

GENERAL 

Read the entire contents of this manual 
before beginning installation. Multiaqua 
assumes no responsibility for equipment 
installed contradictory to any code 
requirement or installation instructions. 

   The components of this fan coil have 
been inspected at the factory and readied 
for shipment. Upon receiving the 
shipment a visual inspection of the 
packaging must be performed.  

   If any damage to the packaging is 
discovered, an inspection of the 
components must be performed and 
noted on the delivery documents. If 
component damage is found a damage 
claim must be filed by the receiving party 
against the delivery party immediately. 

  This product is designed and 
manufactured to permit installation in 
accordance with national codes. It is the 
installer’s responsibility to install the 
product in accordance with national 
codes and/or prevailing local codes and 
regulations.  
  Care must be taken to ensure the 
structural integrity of the supporting 
members, clearances and provisions for 
servicing, power supply, coil connections 
and/or condensate removal. Before the 
installation ensure the structural strength 
of the supporting members is sufficient. 
See 

Figure 1

 for hanging weights of the 

fan coils.  
  
 

-------------------------------------- CAUTION -------------------------------------- 

Care must be taken when handling sheet metal. Sheet metal parts have sharp edges and could 
cause injury.  

This unit is designed to be installed in an  
horizontal configuration only, and into an 
enclosure assembly. The enclosure assembly 
can be ordered separately or field fabricated 
by the installing contractor.  See 

Figure 2

 

for enclosure part numbers, dimensions and 
weights. See 

Figure 3

 for fan coil only 

dimensions. 
  The coil hand of connection is field 
reversible to left or right hand connection. 
See 

Figures 4-6

 

for converting the coil hand 

of connection.   

FAN COIL 

APPROXIMATED 

MODEL NUMBER  WEIGHTS (LBS) 

MHCCW-04 

66.0 

MHCCW-06 

68.2 

MHCCW-08 

72.6 

MHCCW-10 

74.8 

MHCCW-12 

83.6 

      

    Figure 1 

Содержание MHCCW-04

Страница 1: ...Rev 1 2 MHCCW 115 ...

Страница 2: ...installation in accordance with national codes It is the installer s responsibility to install the product in accordance with national codes and or prevailing local codes and regulations Care must be taken to ensure the structural integrity of the supporting members clearances and provisions for servicing power supply coil connections and or condensate removal Before the installation ensure the st...

Страница 3: ... 5 51 21 65 MHCCW06 XX 37 72 34 56 31 41 10 23 5 51 21 65 MHCCW08 XX 37 72 34 56 31 41 10 23 5 51 21 65 MHCCW10 XX 43 70 40 55 37 40 10 23 5 51 21 65 MHCCW12 XX 49 68 46 53 43 38 10 23 5 51 21 65 F E D Water Return Water Supply 1 75 MPT Condensate Drain Connection Both Ends 5 Air Vent Coil Drain B C A Drain Pan Mounting Notches Figure 3 Figure 3 ...

Страница 4: ...at hold the coil into the fan coil frame assembly Four screws per side Figure 5 3 Slide the coil out of the fan coil frame assembly toward the coil supply and return line connections Ensure that care is taken when removing and inserting the coil not to damage the coil fins Insert the coil into the fan coil frame assembly from the other end and reverse procedures 4 5 to reassemble the fan coil Figu...

Страница 5: ... in the next step Figure 7 2 Remove the five screws attaching the blower assembly to the coil assembly Separate the electrical and blower assemblies from the coil assembly Figure 8 3 Insert the coil assembly into the enclosure assembly starting with the discharge air opening of the coil first Ensure that the discharge of the coil is inserted into the discharge of the enclosure completely Failure t...

Страница 6: ...e blower assembly onto the coil assembly using the five screws previously removed in step 2 Figure 8 Figure 11 6 Reinstall the electrical assembly onto the coil assembly using the ten screws previously removed in step 1 Figure 7 Figure 12 ELECTRICAL COIL DRAIN AND RETURN SUPPLY AIR LOCATIONS 7 There are multiple entry points on the factory supplied enclosure assembly for water lines condensate lin...

Страница 7: ...ondensate drain lines have at least one quarter of an inch of fall per foot for proper drainage Figure 14 WATER COIL CONNECTIONS 9 The fan coil unit comes with a manual air bleed and a manual coil drain fitting They are located on the same side as the supply and return water line connections The water supply line is connected to the coil connection furthest away from the fans The water return line...

Страница 8: ... national codes and or local codes and regulations Care must be taken when installing the service access panel to ensure the opening of the hinged service panel Figure 16 17 11 Filters are not supplied with the fan coil unit or the service access panel The filter s must be supplied by the installing contractor If a louvered service access panel is used the filter will mount on the under side of th...

Страница 9: ...oil Size A B C in in in MAP468L NL 4 43 25 27 5 1 5 MAP468L NL 6 43 25 27 5 1 5 MAP468L NL 8 43 25 27 5 1 5 MAP10L NL 10 49 25 27 5 1 5 MAP12L NL 12 55 25 27 5 1 5 Figure 18 FAN COIL MODEL NUMBER RECOMMENDED FILTER SIZES Width in Length in MHCCW04 18 36 MHCCW06 18 36 MHCCW08 18 36 MHCCW10 18 36 MHCCW12 2 qty 18 24 B A C type Figure 17 ...

Страница 10: ...NL 12 6 43 75 Figure 19 12 The fan coil enclosure assembly has a supply air duct flange to allow the attachment of ductwork Ensure when attaching ductwork to the flange that the screws are at least one and half inches away from the front of the enclosure This is to allow proper insertion of the fan coil assembly into the enclosure assembly when duct work will be installed before the fan coil is in...

Страница 11: ... with local national electrical codes and regulations These electrical connections will include over current protection in the form of fuses or circuit breakers Have your contractor identify label the circuits and the location of them so that you may be in a position to make inspections and or replacements in the event the unit fails to operate or is being serviced If fuses are used ensure that th...

Отзывы: