The toilet room itself
The toilet can be placed anywhere you like; it does
not need to have a particular room temperature.
However, the composting process will be more rapid
in a warmer room, as the microorganisms thrive in a
warm environment. It must be possible to conduct
urine away from the toilet. Separera is therefore most
suitable as a summer toilet, as there may be problems
with managing the urine in wintertime.
Air supply
Make sure there is a good air supply, for example,
through a 10 mm gap under the door or via a vent.
Air will be evacuated via the toilet, so cross-draughts
must be avoided.
Ventilation
Install the piping according to the below instructions;
•
Lift off the upper section (1) of the toilet, remove
the inner container (9).
•
Drill or cut a hole in the lower section for the
urine hose, according to chosen option
(7A or 7B).
•
Position the lower section (10) against the
external wall of the room.
•
Mark for wall brackets, ventilation pipe and hose.
•
Measure and drill a hole in the roof for the
ventilation pipe, 55 mm. Saw a hole for the urine
hose (25 mm).
•
Pass the urine hose through the floor/wall
and seal with silicone.
INSTALLATION
5
4
•
Cut the exterior pipe to fit the angle of the roof.
•
Position the roof flashing – use soapy water to
make this easier. For those with a tin roof, it may
be best to get a metal worked to make some
metal flashing.
•
Place the outer pipe with the roof flashing over
the insulated ventilation pipe.
•
Adjust the roof flashing to the external roof and
seal firmly with asphalt sealant between the
flashing and the roof.
•
Once all the piping is insulated and covered, fit
the reducing coupling on the top, and then fit the
insect netting.
•
Place a bag in the composting chamber and fold it
over the edge. Place the container inside the lower
section and check that the metal railing covers the
edge of the urine bowl and that the bag does not
cover the fan. The bag is tightened in the front by
the metal railing and in the back by the handle.
•
Pour approximately 5 litres of Special humus into
the toilet.
IMPORTANT! Insulate the pipe according to the
instructions. Do not use pipe bends over 45 degrees
and avoid having more that two; this is to ensure a
natural draught when the toilet is not in use.
Attachment
W
A
L
spacers
pip
Use no more than 2 pipe bends, and none over 45° angle, to ensure a natural draught.
MAX 45
°
non-
sleeved
sleeved
pipe
RUBBER
FLASHING
sealing using asphalt sealant
roof covering (tile,
felting or tin/plastic)
•
Set the lower section in position and seal between
the floor and the toilet. Connect the urine hose to
the urine bowl. Fix the hose using hose clamps,
being careful not to damage the nipple.
•
Mount the ventilation pipes unsleeved end into the
rubber coupling. Screw the toilet securely to the
wall using screws and washers.
•
Install the ventilation pipe and seal the passage
through the exterior roof using asphalt sealant to
prevent leaks.
•
Insulate all piping that passes through cold spaces
(e.g. in the loft and on the outside of the building)
– this is to prevent condensation.