![Muller HYDRO-GUARD 200 Series Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/muller/hydro-guard-200-series/hydro-guard-200-series_operating-instructions-manual_1853775006.webp)
6
Freeze Protection
The Hydro-Guard® Direct Discharge
Unit (200 Series Warm Climate)
can be upgraded to include freeze
protection via a thermal control
valve to help prevent the unit from
freezing at colder temperatures.
Dechlorination (included)
All Hydro-Guard® Units are
equipped with a dechlorination
system. Dechlorination takes place
as a portion of the discharged
water passes through a housing
containing either sodium sulfite
or ascorbic acid tablets. This
action creates a concentrated
dechlorination solution that
then mixes with the non-directly
treated portion of the discharge to
effectively dechlorinate the entire
discharge volume. This option is
available for the 200 Series Warm
Climate Direct Discharge Unit.
The following is a brief overview
and introduction to Hydro-Guard®
Options.
Sample Station (Included)
A standard feature on the 200
Series Warm Climate High Profile
Direct Discharge Unit is the sample
port, which allows Hydro -Guard's
Portable Sample Valve (Part# HG-S
1167) to attach to the sample port
to obtain a sample. Slip off the
sanitary blue cap, attach the quick-
connect adaptor, open the valve and
collect your sample. You may wish
to run a brief manual mode flush
prior to the collection in order to
ensure water indicative of the main-
line water quality is being sampled.
Generally a two-minute flush is
sufficient. Track your residual levels
and alter flushing frequency and/or
duration in order to maximize water
conservation.
HYDRO-GUARD® FEATURES, OPTIONS AND UPGRADES
Options and Upgrades
200 SERIES WARM CLIMATE HIGH-PROFILE DIRECT DISCHARGE UNIT