U-20808/U-20809 Non-Adjustable Vertical Indicator Posts

General Information

2

3

Approvals and Standards

Model U-20808/U-20809 Indicator 

Posts are listed by Underwriters 

Laboratories Inc. (UL). Model 

U-20808 Indicator Posts are 

approved by Factory Mutual 

Research Corporation.

      WARNING: The Model 

U-20808/U-20809 Indicator Posts 

described herein must be installed 

and maintained in compliance

with this document, as well as 

with the applicable standards 

of the National Fire Protection 

Association, in addition to the 

standards of any other authorities 

having jurisdiction. Failure to do 

so may impair the integrity of 

these devices.
The owner is responsible for 

maintaining their fire protection 

system and devices in proper 

operating condition. The installing 

contractor or manufacturer should 

be contacted relative to any 

questions.
Removing or disabling the tamper 

resistant feature of the special key 

wrench screw (used to secure the 

cover of the Supervisory Control 

Valve Switch) will void its listings 

and approval.

Vertical Indicator Posts are designed 

to operate non-rising stem (inside 

screw) gate valves, which are 

used to control an underground 

water supply to automatic sprinkler, 

water spray deluge, foam-water 

deluge, or standpipe fire protection 

systems. They permit operation of 

underground valves while providing 

an above ground visual indication 

as to whether the valves are open 

or shut, in addition to a means for 

locking the valves in a particular 

position. Indicator posts provide for 

valve operation from outside of the 

protected property and, therefore, the 

opportunity for more prompt valve 

operation in an emergency situation.
U-20808 Indicator Posts will 

accommodate 4” – 14” post indicator 

valves (PIV) requiring 14 to 43 

turns to open and that are listed or 

approved for fire protection system 

service. The U-20809 Indicator Post 

will accommodate 16” – 24” post 

indicator valves requiring 49 to 75 

turns to open.
Indicator Posts are provided 

“Standard Order” for use with left 

hand opening valves; however, 

they may be “Special Ordered” for 

use with right hand opening valves 

or converted in the field for use 

with a right hand opening valve by 

changing the left hand opening Post 

Head to a right hand opening Post 

Head.
Indicator Posts accept direct 

attachment of a 

1

/

2

” NPT mounting 

electric supervisory switching device 

which can be used by proprietary 

and central stations to monitor the 

open position of the Indicator Post. 

Detailed information on attaching 

a UL/FM approved Supervisory 

Control Valve Switch (supplied by 

customer) is given in the Technical 

Data section. 

overview

typical installation

TYPICAL INSTALLATION OF:

U-20808: 4” - 14” Post Indicator Valves 

U-20809: 16” - 24” Post Indicator Valves

Padlock

!

UL/FM 

Approved 

Supervisory

Control 

Valve 

Switch

(supplied by 

customer)

Содержание U-20808

Страница 1: ...training and periodic review regarding the use of this equipment is essential to prevent possible serious injury and or property damage The instructions contained herein were developed for using this...

Страница 2: ...round valves while providing an above ground visual indication as to whether the valves are open or shut in addition to a means for locking the valves in a particular position Indicator posts provide...

Страница 3: ...n be accommodated by each Order Length for the 4 24 USPVH Resilient Wedge PIVs based on the typical diameter of underground pipe For PIVs with different B dimensions the minimum and maximum trench dep...

Страница 4: ...diameter typical for underground pipe Size No D 0 2 1 8 2 14 Dimensions D Nominal Trench depths For USPVH IBBM Double Disc and Resilient Wedge Post Indicator Valves Valve size Number SIZE 0 1 2 4 1 3...

Страница 5: ...t the Post will be plumb and the Stem will run true with the center of the Post Head Coupling clearances can accommodate a maximum pipe slope of 5 degrees It is recommended that a spirit level be used...

Страница 6: ...as appropriate and note the direction in which the Trip Rod must move when the OPEN Target is returned to the Post Window Slide the Switch Assembly as far as possible onto the Nipple while maintaining...

Страница 7: ...ng 290157 20 OPEN Target U 20808 290144 U 20809 290552 21 SHUT Target U 20808 290145 U 20809 290553 22 Hex Bolt U 20808 290191 U 20809 290631 23 Hex Nut 190939 Replacement parts 1 Post Head 2 Barrel 3...

Страница 8: ...e Indicator Post should also be physically tried to be sure that the valve is in the fully open position if there are any damaged parts sign of tampering or the position of the valve is questionable N...

Отзывы: