background image

3

INSTRUCTIONS FOR SENTRYX SOFTWARE 

ENABLED SUPER CENTURION:

The following instructions apply to the installation of the  
Sentryx software enabled Retrofit Kit. For the complete 
hydrant, install the same way as a Super Centurion Fire Hydrant 
(Reference AWWA M17). Once installation is complete, follow 
steps 37-40 below.

1.  Confirm the hydrant is de-pressurized as described above.
2.  Place the hydrant in the closed position.
3.  Remove hold-down nut (Turn opposite of the opening 

direction), anti-friction washer and operating nut  
from bonnet. 

4.  Lubricate outside of brass sleeve and slide over threaded 

stem end to prevent o-ring damage.

5.  Remove bolts (8) from bonnet and remove bonnet. remove 

brass sleeve.

6.  Remove o-ring from upper barrel. Slide slotted end of A-359 

over top of stem and engage the pin in upper stem. Turn ˝T˝ 
head tightening wrench against stem*. 

7.  Pull up on seat wrench to be sure the main valve is 

completely closed. [The main valve must be closed or the 
upper valve plate will be damaged]. Lower support arm onto 
top flange of the upper barrel and tighten thumb screw to 
hold the main valve in the closed position.

8.  Unfasten main valve assembly by turning seat wrench 

counter-clockwise.

9.  Disengage seat wrench from upper stem.
10.  Pull up and remove upper & lower stem, main valve assembly 

and seat ring from hydrant barrel as a unit.

*Review the Seat Wrench Operating Manual (F14285) for 
more seat ring removal information.

CAUTION

MUELLER CO. RECOMMENDS FOLLOWING AWWA M-17 
MANUAL FOR INSTALLATION, FIELD TESTING AND 
MAINTENANCE OF FIRE HYDRANTS. 

Содержание SENTRYX SUPER CENTURION

Страница 1: ... proceed through instructions below Note Caution Changes or modifications not expressly approved by Mueller Systems LLC could void the user s authority to operate the equipment This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in...

Страница 2: ...pletely 3 Open hydrant main valve completely 4 A continuous flow of water no matter how slight indicates hydrant is not properly isolated from the main water supply This issue must be corrected before any hydrant disassembly can proceed i e the water to the hydrant MUST be stopped EQUIPMENT TOOLSNEEDED PPE Hard hat Safety shoes Safety vest Safety glasses Work gloves Tool A 367 brass sleeve A 311 o...

Страница 3: ... remove brass sleeve 6 Remove o ring from upper barrel Slide slotted end of A 359 over top of stem and engage the pin in upper stem Turn T head tightening wrench against stem 7 Pull up on seat wrench to be sure the main valve is completely closed The main valve must be closed or the upper valve plate will be damaged Lower support arm onto top flange of the upper barrel and tighten thumb screw to h...

Страница 4: ...stainless steel lock washer 15 Clean inspect and replace any damaged parts Super Centurion main valve can be reversed to provide a new seal Replace drain valve facings if damaged 16 Reassemble main valve assembly to new lower stem Reverse steps with newly provided brass lower valve nut and tighten to 90 115 ft lbs 17 Assemble the new lower stem via the stem coupling to the upper stem ...

Страница 5: ...to avoid cross threading 21 Reassemble wrench to upper stem Pull up on seat wrench to ensure main valve is completely closed lower support arm and tighten thumb screw while maintaining main valve in the closed position Turn main valve assembly clockwise to 100 190 ft lbs 22 Remove the seat wrench 23 Attach brass sleeve to upper stem and lubricate outside to protect o ring seals from thread damage ...

Страница 6: ... the hold down nut and bonnet o ring 28 Take red plastic spacer and slide over bottom of hold down nut past the o ring and up against the hold down nut shoulder 29 Reassemble operating nut anti friction washer on top thrust collar of operating nut bonnet o ring hold down washer and hold down nut hand tighten to secure in place 30 Torque bonnet bolts 8 to 40 80 ft lbs 31 Torque hold down nut to 200...

Страница 7: ...en drained below the antenna near the top of the lower stem Necessary for the stem to communicate with the bonnet d System water pressure is 20 psi or greater e Re swipe the commissioning tool If success feedback is not received within 5 minutes contact Customer Service Once a Sentryx software enabled Super Centurion has been successfully installed auto locating of hydrant using GPS will automatic...

Страница 8: ... third parties Products above marked with a section symbol are subject to patents or patent applications For details visit www mwppat com These products are intended for use in potable water applications Please contact your Mueller Sales or Customer Service Representative concerning any other application s F 14286 10 20 FormoreinformationaboutMuellerortoviewourfulllineofwaterproducts pleasevisitww...

Отзывы: