504 – AL CAN POM Node Lost
ZKP-Number: 14.500.904
Cause
Corrective action
POM missing on CAN bus.
u
Check connection and POM.
506 – AL Low Starter Voltage
ZKP-Number: 14.500.906
Cause
Corrective action
The battery voltage is too low for
the starting process.
u
Check starter battery and cabling.
507 – AL POM Error
ZKP-Number: 14.500.907
Cause
Corrective action
A general POM fault occurred.
u
Replace POM.
508 – AL Wrong POM-ID
ZKP-Number: 14.500.908
Cause
Corrective action
POM sends a different ID
number than expected.
u
Check POM wiring harness.
510 – AL Override applied
ZKP-Number: 27.002.010
Cause
Corrective action
Override was activated.
u
Deactivate Override pushbutton again.
515 – AL Starter Not Engaged
ZKP-Number: 21.090.926
Cause
Corrective action
Starter on CPM / POM could not
be engaged. If the number of
automatic start attempts from PR
2.1090.134 Number of Start
Attempts is used up then start is
canceled. Check CPM, starter
and cabling.
1. Repeat starting attempt
2. Check CPM, starter and cabling.
126 | Troubleshooting | M015710/04E 2012-09