727 – AL L1 Delta T-NT Intercooler
Cause
Corrective action
The differential temperature at
sensors B26 and B90 has violated
limit value 1. The LT coolant inlet
temperature is too high in relation
to the ambient air temperature.
1. Check cooler (plant side) for contamination.
2. Check operation of fan (plant side).
3. Contact Service.
729 – AL_HI1_T_Exh_DPFsys_inl_F1
Cause
Corrective action
The exhaust gas temperature
before the DOC measured at
sensor B4.33 has violated limit
value 1. The exhaust gas
temperature before the DOC is
too high.
u
Contact Service.
730 – AL_HI2_T_Exh_DPFsys_inl_F1
Cause
Corrective action
The exhaust gas temperature
before the DOC measured at
sensor B4.33 has violated limit
value 2. The exhaust gas
temperature before the DOC is
too high.
u
Contact Service.
731 – AL L1 T-Exhaust DPF Inlet 1
Cause
Corrective action
The exhaust gas temperature
before the DPF measured at
sensor B4.31 has violated limit
value 1. The exhaust gas
temperature before the DPF is too
high.
u
Contact Service.
732 – AL L2 T-Exhaust DPF Inlet 1
Cause
Corrective action
The exhaust gas temperature
before the DPF measured at
sensor B4.31 has violated limit
value 2. The exhaust gas
temperature before the DPF is too
high.
u
Contact Service.