![MTU 12V 2000 G23 Скачать руководство пользователя страница 137](http://html1.mh-extra.com/html/mtu/12v-2000-g23/12v-2000-g23_use-and-maintenance-manual_1852657137.webp)
Troubleshooting
5 – 15
Fault code
Alarm text
Meaning
Task
354
OPEN_LOAD
CYL. B4
Disconnection in wiring to
solenoid valve cylinder B4;
Misfiring
1. Check wiring.
2. Contact Service.
355
OPEN_LOAD
CYL. B5
Disconnection in wiring to
solenoid valve cylinder B5;
Misfiring
1. Check wiring.
2. Contact Service.
356
OPEN_LOAD
CYL. B6
Disconnection in wiring to
solenoid valve cylinder B6;
Misfiring
1. Check wiring.
2. Contact Service.
357
OPEN_LOAD
CYL. B7
Disconnection in wiring to
solenoid valve cylinder B7;
Misfiring
1. Check wiring.
2. Contact Service.
358
OPEN_LOAD
CYL. B8
Disconnection in wiring to
solenoid valve cylinder B8;
Misfiring
1. Check wiring.
2. Contact Service.
359
OPEN_LOAD
CYL. B9
Disconnection in wiring to
solenoid valve cylinder B9;
Misfiring
1. Check wiring.
2. Contact Service.
360
OPEN_LOAD
CYL. B10
Disconnection in wiring to
solenoid valve cylinder B10;
Misfiring
1. Check wiring.
2. Contact Service.
361
POWER STAGE
FAIL 1
Defect in ECU (solenoid valve
power stage)
Contact Service.
362
POWER STAGE
FAIL 2
Defect in ECU (solenoid valve
power stage)
Contact Service.
363
STOP POWER
STAGE 1
Solenoid valve or wiring or
ECU defective
automatic engine shutdown
1. Check wiring.
2. Try to re-start the engine
(
→
Page 3 – 03).
3. Contact Service.
364
STOP POWER
STAGE 2
Solenoid valve or wiring or
ECU defective
automatic engine shutdown
1. Check wiring.
2. Try to re-start the engine
(
→
Page 3 – 03).
3. Contact Service.
365
STOP
MV-WIRING
Solenoid-valve wiring faulty;
automatic engine shutdown
1. Check wiring.
2. Try to re-start the engine
(
→
Page 3 – 03).
3. Contact Service.
381
TRAN.OUT1
PLANT DEF
Binary transistor output plant 1
defective
Contact Service.
382
TRAN.OUT2
PLANT DEF
Binary transistor output plant 2
defective
Contact Service.
383
TRAN.OUT3
PLANT DEF
Binary transistor output plant 3
defective
Contact Service.
384
TRAN.OUT4
PLANT DEF
Binary transistor output plant 4
defective
Contact Service.
M015560
/
00E 03-05 © MTU
Содержание 12V 2000 G23
Страница 4: ......
Страница 10: ...1 II Table of Contents M015560 00E 03 05 MTU...
Страница 20: ...1 10 Safety M015560 00E 03 05 MTU...
Страница 22: ...2 II Table of Contents M015560 00E 03 05 MTU...
Страница 94: ...3 II Table of Contents M015560 00E 03 05 MTU...
Страница 104: ...3 10 Operation M015560 00E 03 05 MTU...
Страница 106: ...4 II Table of Contents M015560 00E 03 05 MTU...
Страница 120: ...4 14 Maintenance Schedule Application Group 3A M015560 00E 03 05 MTU...
Страница 121: ...Table of Contents 5 I 5 Troubleshooting 5 1 Troubleshooting 5 01 5 2 ECU alarms 5 04 M015560 00E 03 05 MTU...
Страница 122: ...5 II Table of Contents M015560 00E 03 05 MTU...
Страница 199: ...Ventilator Drive 6 59 Final steps 1 Install guard cover 2 Fit screws and tighten M015560 00E 03 05 MTU...
Страница 206: ...6 66 Engine Governor Electronic Control System M015560 00E 03 05 MTU...
Страница 207: ...Table of Contents 7 I 7 Annex 7 1 Abbreviations 7 01 7 2 Index 7 03 M015560 00E 03 05 MTU...
Страница 208: ...7 II Table of Contents M015560 00E 03 05 MTU...