Fault code
No.
Designation
Meaning
Task
Related
parameter
No.
362
AL Power Stage High
Alarm configuration; Internal
electronic fault (electronics
possibly faulty: Start ITS). If
the ITS diagnosis result is
"electronics OK", note fur‐
ther fault messages (e.g.
cabling faults).
1. Check solenoid
valve cabling.
2. Replace engine
governor.
1.8004.49
7
363
AL Stop Power Stage
Alarm configuration; Internal
electronic fault (electronics
possibly faulty: Start ITS).
1. Check cabling.
2. Attempt to re‐
start engine.
1.8004.56
0
365
AL Stop MV-Wiring
Ground
Alarm configuration; Injector
cabling fault. If bit
"1.1020.021" (Power Stage
Failure: Stop Engine) is set,
engine will be shut down as
additional measure. 1. Short
circuit of positive connection
of one or more injectors to
ground 2. Short circuit of
negative connection of one
or more injectors to ground .
1. Check cabling.
2. Attempt to re‐
start engine.
1.8004.56
1
371
AL Wiring TO 1
Alarm configuration; Short
circuit or wire break on tran‐
sistor output 1 (TO 1).
1. Check turbo‐
charger valve/ca‐
bling, repair as
necessary
2. Replace engine
governor.
1.8004.63
4
372
AL Wiring TO 2
Alarm configuration; Short
circuit or wire break on tran‐
sistor output 2 (TO 2).
1. Check recircula‐
tion valve/cabling,
repair as necessa‐
ry
2. Replace engine
governor.
1.8004.63
5
373
AL Wiring TO 3
Alarm configuration; Short
circuit or wire break on tran‐
sistor output 3 (TO 3).
-
1.8004.63
6
374
AL Wiring TO 4
Alarm configuration; Short
circuit or wire break on tran‐
sistor output 4 (TO 4).
-
1.8004.63
7
381
AL Wiring TOP 1
Alarm configuration; Short
circuit or wire break on tran‐
sistor output, plant-side 1
(TOP 1).
Check cabling to
plant.
2.8006.63
8
382
AL Wiring TOP 2
Alarm configuration; Short
circuit or wire break on tran‐
sistor output, plant-side 2
(TOP 2).
Check cabling to
plant.
2.8006.63
9
56 | Troubleshooting | MS150054/02E 2012-02