32
Stator Wiring
The locked rotor stator current is equal to the amplifiers continuous rating and for either
low speed or locked rotor conditions the stator must withstand this continuous rating.
Derating the stator wiring for three phase operation should not be done.
Model
Locked Rotor
MPA-05-460
5 amps
MPA-09-460
9 amps
MPA-15-460
15 amps
MPA-25-460
25 amps
MPA-35-460
35 amps
MPA-50-460
50 amps
MPA-75-460
75 amps
MPA-100-460
100 amps
For operation at 460 Vac it is recommended that the stator wiring insulation withstand 600
volts.
MOTOR
FRAME
T S
R
T
S
R
AC INPUT
A GND connection is supplied as a means to ground the motor frame to earth ground.
If shielded cable is not used, it is recommended that the RST and GND wires be twisted.
NOTE
If the resolver feedback wiring is to be run
adjacent to the RST motor wiring, then the
motor wiring should be 100% shielded (foil
and braid).
Содержание MPA-05-460
Страница 12: ...12 ANF3 User Configuration Locations NOTE Never change DIP switches or jumpers with power ON...
Страница 35: ...35 Shunt Amplifier Wiring...
Страница 36: ...36 EXS 50 100 460 Mechanical Footprint 0 5 6 16 0 15 5 0 5 0 0 1 0 8 5 9 5...
Страница 38: ...38 Inductor Mechanical Footprint loose parts Typical IND 100 5mH 5 25 4 81 44 0 0 42 3 85 4 27 6 35 0...
Страница 39: ...39 Typical IND 25 460 2mH 4 60 0 3 39 3 10 29 0 0 25 3 05 3 30 20 3 75 Clearance...
Страница 41: ...41 Typical S Three Phase 460V Amplifiers...
Страница 45: ...45 Typical Wiring...