17
INM4500-2
Mar 2009
6.1.4 MTL4513 - Switch/Proximity detector interface
Two-channel, with line fault detection and phase reversal
The MTL4513 enables two solid-state outputs in the safe area to be controlled by two switches
or proximity detectors located in the hazardous area. The Ch1/Ch2 output transistors share a
common terminal and can ve or -ve polarity signals.
Line Fault Detect
and
Phase
Reversal
for the channel are selected by DIL switches on the side of the module. LFD indication is
provided on the top of the module.
See Section 5.1.1 on page 8 for LFD and PR switch details.
Channel 1 & 2
switch settings
apply.
For switch sensor inputs, with LFD selected, make sure resistors (22k
Ω
and 680
Ω
) are fi tted.
Note
: Signal plug HAZ1-3 is required for access to the earth leakage detector function.
PWR
STS
LFD
STS
LFD
MTL4513
CH2
CH1
Figure 6.4
LED indicators
for MTL4513
Terminal
Function
1
Input –ve (Ch 1)
2
Input +ve (Ch 1)
3
To earth leakage detector
4
Input –ve (Ch 2)
5
Input +ve (Ch 2)
6
To earth leakage detector
7
Output (Ch 1)
8
Output (Ch 1/Ch 2)
9
Output (Ch 2)
13
Supply
–ve
14
Supply
+ve
Hazardous area
Safe area
+
+
1 2 3 4 5 6
7 8 9 10 1112
13 14
Vs+
Vs
2035V dc
Ch 1
Ch 1
Ch 2
Ch 2
22k
W
680
W
22k
W
680
W
To MTL earth leakage detector
Switch-type sensors
require resistors
if LFD is selected
Содержание MTL4500 Series
Страница 1: ...MTL合作伙伴 滨州新大新机电科技有限公司 Instruction Manual INM4500 MTL4500 Series isolating interface units ...
Страница 2: ...ii INM4500 2 Mar 2009 ...
Страница 49: ...45 INM4500 2 Mar 2009 ...
Страница 50: ...46 INM4500 2 Mar 2009 ...
Страница 51: ...47 INM4500 2 Mar 2009 ...