8
INM9469-3
June 2012
17 ATEX & IECEX CERTIFICATION INFORMATION
The following information is in accordance with the Essential Health and Safety Requirements
(Annex II) of the EU Directive 94/9/EC [the ATEX Directive - safety of apparatus] and is provided
for those locations where the ATEX Directive is applicable.
General
a) This equipment must only be installed, operated and maintained by competent personnel.
Such personnel shall have undergone training, which included instruction on the various types
of protection and installation practices, the relevant rules and regulations, and on the general
principles of area classification. Appropriate refresher training shall be given on a regular
basis. [See clause 4.2 of EN 60079-17].
b) This equipment has been designed to provide protection against all the relevant additional
hazards referred to in Annex II of the directive, such as those in clause 1.2.7.
c) This equipment has been designed to meet the requirements of intrinsically safe electrical
apparatus in accordance with EN 60079-0, EN 60079-11 and EN 60079-26.
Installation
a) reference to the IEC code of practice IEC 60079-14. In addition, particular industries or end
users may have specific requirements relating to the safety of their installations and these
requirements should also be met. For the majority of installations the Directive 1999/92/EC
[the ATEX Directive - safety of installations] is also applicable.
b) Unless already protected by design, this equipment must be protected by a suitable enclosure
against:
i) mechanical and thermal stresses in excess of those noted in the certification documentation
and the product specification.
ii) aggressive substances, excessive dust, moisture and other contaminants.
c) This equipment is intrinsically safe electrical apparatus and is normally mounted in a
hazardous area. When mounted in a Zone1 location the apparatus must be provided
with an enclosure, which offers an additional degree of protection appropriate to the area
classification.
Read also the Special Conditions for Safe Use for any additional or more specific information.
Special Conditions for Safe Use
1. When used with Group I gases, the Modules shall each be mounted within an enclosure
providing a degree of protection of at least IP54, in accordance with EN 60529, and in a
manner that does not impair the existing creepage and clearance distances. The enclosure shall
also comply with the requirements of Clauses 7 and 8 of EN 60079-0:2006.
2. The connectors do not meet the ingress protection rating of IP20, therefore, this shall be taken
into consideration during the installation of the 9400 Series Ethernet Modules when used with
Group II gases, and each module shall be provided with an enclosure that is commensurate
with the environment into which it is installed.
3. The supply to the modules must be derived from a suitably certified, intrinsically safe supply.
Inspection and maintenance
a) Inspection and maintenance should be carried out in accordance with European, national
and local regulations which may refer to the IEC standard IEC 60079-17. In addition specific
industries or end users may have specific requirements which should also be met.
b) Access to the internal circuitry must not be made during operation.
Repair
This product cannot be repaired by the user and must be replaced with an equivalent certified
product.
Marking
Each device is marked in accordance with the Directive and CE marked with the Notified Body
Identification Number.
This information applies to products manufactured during or after the year 2012.