MAINTENANCE AND OPERATING MANUAL
Chapter 7 - Electronic Board
The data inside this manual are not binding and they can be modified by the manufacturer without notice.
All rights reserved.
TAEevo015÷351
C
HAPTER
7
E
LECTRONIC
B
OARD
7 . 1
D i s p l a y
The display is divided in 3 zones.
7.1.1 Display icons
7 . 2
F u n c t i o n o f b u t t o n s
Top-left zone
It displays the temperature of temperature regulation probe.
NOTE
The displaying depends on the setting of parameter
CF36
(see chapter
7.9 “
Values displayed”
).
Bottom-left zone
It displays the operating setpoint, OFF with stand-by unit.
NOTE
The displaying depends on the setting of parameter
CF42
(see chapter
7.9 “
Values displayed”
).
Right zone
Signalling icons.
ICON
MEANING
ICON
MEANING
Celsius degrees (If displayed)
Low pressure alarm
Fahrenheit degrees (If not displayed)
$
Antifreeze resistance
Bar/Psi
D
Pump on
Compressor 1
Flow meter alarm
Compressor 2
Time to defrost starting
P
Stand-by unit
B
Fans on
General alarm
Indication for Function Menu entering
High pressure alarm
BUTTON
FUNCTION
)
It selects water temperature and ambient air temperatures in the top part of the display.
During programming phase it scrolls the parameter’s codes or increases their values.
&
If pressed for 5 seconds, it allows to switch on or off the unit in chiller modality.
It selects water temperature in the top part of the display. During programming phase it
scrolls the parameter’s codes or decreases their values.
-
If pressed for 5 seconds, it allows to display or modify the set point.
During programming phase it selects a parameter of confirms a value.
*
It allows to enter Function Menu.