TAEevo015÷351
21
MAINTENANCE AND OPERATING MANUAL
Chapter 6 - Start up
The data inside this manual are not binding and they can be modified by the manufacturer without notice.
All rights reserved.
TAEevo015÷351
C
HAPTER
6
S
TART
UP
ATTENTION
Before starting up these units be sure that all personnel have read and understood the Chapter 2
“Safety”
.
1.
Check that the machine's on/off valves are open.
2.
Check that the tank is completely full of water and properly vented .
3.
Carry out the level sensor calibration as indicated in the 8.5 “Level sensor” paragraph
4.
Check that the ambient temperature is within the limits indicated in the machine data plate.
5.
It is possible to check that the pressure is about 0.5 bar on the manometer located on the back of the unit (only if the water circuit is
of the closed type).
6.
Check that the main switch is in the OFF position (“0”).
7.
Check that the power supply voltage is correct.
8.
Power the machine by means of the supply line protection device.
9.
Turn the machine main switch ON (“I”).
10.
Check that the water flows across the evaporator.
11.
Press
'
button for 5 seconds
if you want to start the unit.
The led
flashes for 5 seconds and then it remains lit.
To
power-off
the machine, press the
'
key.
12.
In three-phase units, check that compressor works correctly (it must not be noisy or overheated) and check that the fans and the
pump (if installed) rotation direction is correct.
If necessary invert two phases of supply.
13.
Check that the pressure difference between the value read on the manometer located on the machine control panel with the pump in
motion and the value read with the pump stopped is higher than the available pressure with the pump's maximum flow capacity. If
this difference is lower, it means that the water flow capacity is higher than the maximum value allowed. In order not to damage the
pump, it is necessary to increase the pressure drop of the hydraulic circuit by, for example, partially closing a pump discharge cock.
14.
Models with centrifugal fans:
Check that the output of the centrifugal fans is correctly ducted and that the pressure drop of the ducting system is about equal to the
available head. If the pressure drops are:
- greater this means that there is a reduction in the flow of cooling air with a consequent drop in machine performance and the
possibility of protection devices tripping even at relatively low ambient temperatures;
- lower this means that the air flow may be too high for the fan and this could be dangerous for the centrifugal fan motor.
15.
If with the first start-up, there is a high ambient temperature and the temperature of the water in the hydraulic circuit is much higher
than the working value (e.g. 25-30°C) this means that the
chille
r starts up overloaded with the consequence of possible tripping
of the protection devices. To reduce this overload, a
chille
r outlet valve can be gradually (but not totally!) closed to reduce the
flow of water passing through it. Open the valve as the water temperature in the hydraulic circuit reaches the working value.
16.
The machine is now
ready for operating
.
If the thermal load is lower than that produced by the unit, the water temperature drops until it reaches the set point (ST01
parameter) set following the instruction of chapter Electronic Board.
When SET-POINT value has been reached, the electronic control controlling the water inlet temperature stops the compressor. The
water pump, on the other hand, is always in motion.