6.4

 

Faults 

The PX2 detector includes a diagnostic module for the continuous monitoring of the relevant functions and 
parameters  as  well as a  processor-independent  watchdog. These  features  set the PX2 device into the safe 
mode  "Fault"  in  case  of  an  internal  or  external  error.  The  following  table  6.1  shows  all  possible  errors, 
possible causes, the related troubleshooting and the resulting device status. 
When the cause of the error has been eliminated, the PX2 gas detector restarts with the diagnostic mode on 
its own. It is not necessary to acknowledge the error message. 
If an error occurs, it is output in the option with display instead of the measured value and in the menu error 
status in plain text. If there is more than one error, it is output with a cumulative, bit-coded error code. 

Error type 

Cause 

Remedy 

Fault 
Relay 

Analog 
Output 

Centr. 
Bus 

Display 

Error Code  Text Mess. 

Sensor Head (SX1) 

DP1- 

Sensor element defective 

Internal 

Replace SX1 
sensor head 

Error 

< 2 mA 

Error code 
is sent

 

0x8 001 h  Sensor  

Temperature < -25 °C > +60 °C 

0x8 002 h  Overtemp. 

Measured value processing 

0x8 002 h  ADC error 

System voltages <> 

0x8 004 h  Voltage 

Operating volt.< 18.5  V> 36.5 V 

0x8 004 h  Voltage 

RAM / ROM / µC error 

0x8 008 h  CPU error 

EEPROM error 

0x8 010 h  EE error 

Meas. value < -6 % of range 

Sensor drift, 
calibration not 
correct 

Perform 
calibration 

0x8 100 h  Underrange 

Meas. value > 106 % of range 

> 21.2 mA 

0x8 200 h  Overrange 

Gas  concentration 
> meas. range 

See 6.2 

Maintenance due 

Maintenance date 
reached 

Perform 
maintenance 

No effect 

Mainten. 
message 

0x8 080 h*  Maintenance 

I / O Unit (PX2) 

EP1- 

Temperature < -25 °C > +60 °C 

 

Ambient temp. 

Temp.!  

Error 

< 2 mA 

Error code 
is sent 

0x8 040 h  Overtemp. 

Internal 

Replace PX2 
device 

Measured value processing 

0x8 002 h  ADC error 

 
RAM / ROM / µC error 

0x8 008 h  CPU error 

EEPROM error 

0x8 010 h  EE error 

No response alarm relay 

0x8 020 h  I/O error 

Configuration error 

Meas. range SX1 ≠ 

I/O unit 

Adjust meas. 
range 

0x8 010 h  EE error 

Deviation of analog output signal 
 < 5 % > 

Short-circuit 

or 

Interruption  at  the 
analog output 

Check wiring / 
load 

Error 

X mA 

0x8 020 h  I/O error 

Internal 

Replace PX2 
device 

Communication error to sensor 
head 

Sensor head not 
fitted correctly / 
wrong gas type 

Check it , set 
correct gas 
type  

Error 

< 2 mA 

0x9 000 h 

Communic. 
error 

Internal 

Replace SX1 
sensor head 

Hardware Watch Dog triggered

 

Internal, < system 
voltage, µC defect. 

Replace PX2 
device 

Error 

< 1 mA 

Comm. 
STOP 

Reset 

Reset 

Operating voltage limits exceeded 
too high / too low 

External 

Check voltage 

Error 

< 2 mA 

Comm. 
STOP 

0x8 008 h 

Voltage 

Internal 

Replace PX2 
device 

Maintenance due 

Maintenance date 
reached 

Perform 
maintenance 

No effect 

0x8 080 h*  Maintenance 

Special Mode 

See chapter 

“Special Mode”

 

Cancel cause 
of Special 
Mode 

Error 

<  
2 mA** 

Comm. 
STOP 

0x8 000 h 

 

Table 6.1: Error messages 

* Is only faded in if an error code is pending. 
** No influence on the analog signal if the Special Mode was triggered by the operator.  

Содержание PolyXeta 2 Series

Страница 1: ...otice MSR Electronic GmbH Buergermeister Schoenbauer Str 13 D 94060 Pocking www msr electronic de Gas Detector Series PolyXeta 2 with Semi conductor Sensor for Freon Gases and Refrigerants for Zone1 a...

Страница 2: ...ective 2014 34 EU 5 1 7 2 Marking and Certificates according to IECEx only for PX2 1 5 1 7 3 Terms and Conditions for Safe Use 5 1 7 4 Listing of Freon Gases 6 1 7 5 Listing of Ammonia 7 2 General Des...

Страница 3: ...20 8 4 Calibration 20 8 4 1 Preliminaries 20 8 4 2 Procedure for Calibration with Tool or Display 21 8 4 3 Extended Calibration 21 8 5 Repairs 21 9 Exchange of Sensor Head 22 9 1 General Notes 22 9 2...

Страница 4: ...Furthermore the operating instructions Service Tool and Display for Gard 2 PolyGard 2 PolyXeta 2 must be read and obeyed if the PolyXeta 2 has a display or if the Service Tool is used The product can...

Страница 5: ...by the conformity declaration of the manufacturer 1 7 1 Marking and Certificates according to ATEX Directive 2014 34 EU PX2 1 Zone 1 und 2 Sensorkopf SX1 PX2 2 Zone 2 Marking II 2G Ex db IIC T4 Gb 01...

Страница 6: ...ir 2070 06 R403a R22 HCFC 2000 ppm Air 2070 07 R408a R22 HCFC 2000 ppm Air 2070 08 R409a R22 HCFC 2000 ppm Air 2070 09 R411a R22 HFC 2000 ppm Air FR07 2077 01 R134a R134a HFC 2000 ppm Air 2077 02 R407...

Страница 7: ...roof stainless steel housing Ex d with an external thread NPT All sensor data are stored in the sensor head After the end of the calibration period or at the end of the sensor lifetime the sensor can...

Страница 8: ...n and minimum variation in temperature In case of very difficult environmental conditions caused by dripping splash rain condenser water or dusts in the atmosphere which are above the IP 65 dust and w...

Страница 9: ...0 Pocking www msr electronic de Depending on the housing version the inlets 2 and 4 are tightly closed or closed by blind plugs Fig 3 1 Dimensions and Mounting NPT3 4 ANSI B1 20 1 Internal Thread NPT...

Страница 10: ...bly of the display is described in chapter 11 Only a professional should perform the wiring and the connection of the electrical installation according to the wiring diagram in compliance with the rel...

Страница 11: ...000 800 700 500 Operating voltage with central bus 0 5 900 500 400 300 1 0 900 900 800 700 Table 4 1 Cables 1 The max cable lengths and our recommendation don t consider any local conditions like fire...

Страница 12: ...sed calibration and test record as well as in the PolyXeta 2 configuration card Necessary changes of parameters for adaptation to the application can be done by qualified persons only in the display a...

Страница 13: ...2 4 20 mA1 3 OK5 Communication OK Maintenance mess 2 4 20 mA1 3 OK5 Communication OK Special mode 6 7 2 mA8 7 Error4 Communication OK Detected fault 6 7 2 mA 7 Error4 Communication OK Processor failu...

Страница 14: ...or Specification from the column Warm up periods During warm up the yellow LED flashes every 2 seconds and Power ON appears in the display The device status during warm up is given in Table 5 2 Status...

Страница 15: ...only locally on the device having released the alarm by manually pressing 5 sec the internal button fig 4 1 or by activating the ESCAPE button on the optional display or the external service tool The...

Страница 16: ...004 h Voltage RAM ROM C error 0x8 008 h CPU error EEPROM error 0x8 010 h EE error Meas value 6 of range Sensor drift calibration not correct Perform calibration 0x8 100 h Underrange Meas value 106 of...

Страница 17: ...period In environments contaminated with such substances calibration has to be performed more frequently to ensure reliable operation Dust deposits at the gas inlet can significantly extend the respon...

Страница 18: ...onal and status messages of the gas warning devices with displays Operation indication green LED ON Alarm indication red LED OFF no alarm Fault indication yellow LED OFF no fault Keep a report about t...

Страница 19: ...quirement the measuring devices have to be calibrated at regular intervals The system control has to be carried out by a qualified person at least every 12 months and includes at least the following a...

Страница 20: ...ype according to table 10 2 column Calibration gas Relative measurement inaccuracy 2 rest is synthetic air 10 RH 8 4 Calibration A routine for comfortable zero and gain calibration is integrated in th...

Страница 21: ...min The processor input voltage must be measured against ground at the test pin led out and if stable 180 s then set to 1650 mV using the potentiometer Stop and remove gassing and wait until the senso...

Страница 22: ...t the sensor head plug in the housing and stretch the cord so that it can follow the rotation of the sensor head Loosen the sensor head with a wrench M24 Unscrew the sensor head carefully stretch the...

Страница 23: ...ero point Zero and gain are necessary see section 8 4 Certain substances and gases in the monitored ambient can affect the sensitivity of the sensor element or destroy the sensor completely This is ca...

Страница 24: ...e for calibration Reaction time Respons e time t90 Respons e time t90 Run in time Flow rate Warm up time Meas range Gas type Range Value indication 4 20 mA signal SX1 Freon group Gas Zero Gain Zero Ga...

Страница 25: ...IL and pull it carefully to the front Put the display board in a dry clean and protected place Now you have access to the connector of the sensor head and can exchange it It is still necessary to dism...

Страница 26: ...opening the housing cover via the four control icons by moving the Magnet_Pen briefly over the respective control icon 11 4 Menu The device parameters and measured values can be read in the menu Para...

Страница 27: ...07 A Yes 18 R409a 20 2000 ppm S2070 08 A Yes 19 R411a 20 2000 ppm S2070 09 A Yes 20 R134a 20 2000 ppm S2077 01 A Yes 21 R407a 20 2000 ppm S2077 02 A Yes 22 R416a 20 2000 ppm S2077 03 A Yes 23 R417a 2...

Страница 28: ...changes STL06 PX2 X7 No 04 PC Software Set for display calibration addressing and parameter changes PCE06 PX2 XF No 05 Cable gland for ATEX IECEx protection type Ex db zone 1 out of brass with certifi...

Страница 29: ...ons also for spare parts and accessories Temperature range 10 C to 40 C 14 F to 104 F Humidity range 40 70 RH not condensing Pressure range 800 to 1200 mbar 80 to 120 kPa Storage time1 Max 6 months Se...

Страница 30: ...x BVS 16 0038X Ignition protection type Ex db II C T4 25 C Ta 60 C Marking II 2G Ex db IIC T4 Gb EMC testing EN 50270 2015 interference immunity interference emission Type 2 industrial use Approvals a...

Страница 31: ...egistered trademark of MSR Made in Germany GAPX2_Freon_E_2020_05_18 Phone 49 8531 9004 0 Fax 49 8531 9004 54 Specification subject to change without notice MSR Electronic GmbH Buergermeister Schoenbau...

Страница 32: ...Page 32 PolyXeta is a registered trademark of MSR Made in Germany GAPX2_Freon_E_2020_05_18 Phone 49 8531 9004 0 Fax 49 8531 9004 54 Specification subject to change without notice MSR Electronic GmbH...

Страница 33: ...Page 33 PolyXeta is a registered trademark of MSR Made in Germany GAPX2_Freon_E_2020_05_18 Phone 49 8531 9004 0 Fax 49 8531 9004 54 Specification subject to change without notice MSR Electronic GmbH...

Страница 34: ...Page 34 PolyXeta is a registered trademark of MSR Made in Germany GAPX2_Freon_E_2020_05_18 Phone 49 8531 9004 0 Fax 49 8531 9004 54 Specification subject to change without notice MSR Electronic GmbH...

Страница 35: ...Page 35 PolyXeta is a registered trademark of MSR Made in Germany GAPX2_Freon_E_2020_05_18 Phone 49 8531 9004 0 Fax 49 8531 9004 54 Specification subject to change without notice MSR Electronic GmbH...

Страница 36: ...Page 36 PolyXeta is a registered trademark of MSR Made in Germany GAPX2_Freon_E_2020_05_18 Phone 49 8531 9004 0 Fax 49 8531 9004 54 Specification subject to change without notice MSR Electronic GmbH...

Страница 37: ...isposed of with the household waste It can be sent back for disposal to your national distribution organization Don t hesitate to contact them if there are any questions on disposal 17 Definitions War...

Страница 38: ...SR Electronic GmbH Buergermeister Schoenbauer Str 13 D 94060 Pocking www msr electronic de 18 History of Document Versions Version Date Author Reason for change Comments 1 0 17 12 2018 G Niedermeier B...

Отзывы: