17
Version 1.0
Operating manual
SOA-1022
Table 10 – Menu «Оборудование»
Position
№
Name
Description
1
ID
AHU network address
2
Имя
AHU name
3
Состояние
AHU status (“Инициализация”
– initialization, “В работе” –
operating, “Предупреждение” – warning, “Тревога” – alarm)
4
Общ.Тест
To test all connected AHUs for operation errors
5
Общ.Сброс
To reset all removed errors of connected AHUs
6
To set up default parameters for all connected AHUs
7
To set up name and ID number for a new AHU
8
To edit heating parameters of the selected AHU
9
To delete the selected AHU
10
ОК
To return to the main screen
11
Отмена
To return to the main screen
Table 11 describes parameters which are displayed after pressing “
” button.
Table 11 – Description of parameters
Parameter
Default value
Описание
Имя
–
AHU name
(this line appears only while editing one AHU)
Задание t
зад
, °С
20.0
To set up required temperature inside dome “t
set
”
Нижняя граница
гистерезиса -t, °С
0.0
Heating will switch on when the temperature falls lower
than “t
set
– 0.0”
Верхняя граница
гистерезиса +t, °С
5.0
Heating will switch off when the temperature rises
higher than “t
зад
+ 5.0”
Нижняя допустимая
граница t
н
, °С
–40.0
If the temperature is lower than the specified one, THs
are switched on forcefully
Верхняя допустимая
граница t
в
, °С
70.0
If the temperature is higher than the specified one, THs
are switched off forcefully
Нижняя допустимая
граница I
н
, А
0.1
If current values of THs are lower than the specified
ones, alarm actuates
Верхняя допустимая
граница I
в
, А
10000.0
If current values of THs are higher than the specified
ones, alarm actuates
Время на нагрев Т
н
, с
600.0
Time (Т
н
) required for temperature increase inside dome
when THs are switched on.
If time is exceeded, alarm actuates