FlameGard 5 MSIR HART
10.30
Command #157: Set Warning Relay Latched Status
This sets the warning relay to either latched or un-latched. If the DIP override flag is set, then the command will
return an ACCESS RESTRICTED code.
Request Data Bytes
Byte
Format
Description
0
Unsigned-8
Relay setting: 1 = latched, 0 = un-latched
Response Data Bytes
Byte
Format
Description
0
Unsigned-8
Relay setting: 1 = latched, 0 = un-latched
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1 - 15
Undefined
16 Error
Access
Restricted
17 - 127
Undefined
10.31
Command #158: Read Warning Relay Latched Status
This reads the latched status of the warning relay.
Request Data Bytes
Byte
Format
Description
0 N/A
N/A
Response Data Bytes
Byte
Format
Description
0
Unsigned-8
Relay setting: 1 = latched, 0 = un-latched
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1-127
Undefined
10.32
Command #159: Set Warning Relay De-Energized/Energized Status
This sets the warning relay to either De-Energized or Energized. If the DIP override flag is set, then the
command will return an ACCESS RESTRICTED code.