11
FlameGard 5 MSIR HART
Test the Remote Alarm.
Request Data Bytes
Byte
Format
Description
0
Bits
Test Remote Alarm: 0 = Turn off, 1 = Turn on Alarm
Response Data Bytes
Byte
Format
Description
0
Bits
Test Remote Alarm: 0 = Alarm Off, 1 = Alarm On
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1-127
Undefined
10.10
Command #137: Read Instrument Temperature (MODBUS Reg 0x14)
Read the temperature of the instrument.
Request Data Bytes
Byte
Format
Description
None N/A
N/A
Response Data Bytes
Byte
Format
Description
0 - 1
Signed-16
Temperature Value
2 Enum
Degrees
Celsius
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1-127
Undefined
10.11
Command #138: Set/Reset Test Lamp Mode (MODBUS Reg 0x5A)