Use the strain relief for the
connection cable "from the
bottom" or "from the top"
installation type
(small/large) .
Select the size based on the
cable diameter.
C
Connection to the power grid
Power grid connection requirements
WARNING! The installation may only be carried out by qualified electrician
WARNING! Make sure again that the connection cable is disconnected from the mains.
The electrical connection to the power grid must be carried out by a qualified electrician. On the
basis of professional training, knowledge of the relevant standards and experience, he/she has the
ability to assess the installation steps and to identify any possible dangers.
On the building side, it is necessary to provide RCD type A circuit breaker (30mA AC). The wallbox
already has an integrated DC residual current detection. The overcurrent protection device of the
electrical supply line must also be dimensioned and installed by an electrician.
Observe the 5 safety rules for electrical work.
NOTE: After connection or reconnection, the electrotechnical
equipment must be tested in accordance with the applicable standards.
NOTE: The operator must provide protection against the lightning.
Connecting the power cable
NOTE: The electrician is responsible for dimensioning the cables according to the
building conditions.
Danger! Voltage! Connection only in a voltage-free state and by an electrician.