After removal of drain pan plug(s), check drain hole(s) 

to verify that drain opening is fully open and free of any 

debris.  Also  check  to  make  sure  that  no  debris  has 

fallen into the drain pan during installation that may plug 

up the drain opening.

Connect the main drain and route downward to drain line 

or sump. Do not connect drain to a closed waste system. 

 be connected and routed to a 

The following best practices are recommended to ensure 

better condensate removal:

• 

than both drain connections at drain pan.

• 

homeowner will notice drainage.

• 

vented and a trap installed. Refer to local codes.

Proper air volume MUST be provided over the evaporator 

coil. To ensure that the static pressure is within the proper 

range, take a draft gauge reading as follows:

Access panel must be removed before drilling air test 

holes.

ABOVE

FINISHED

SPACE?

OVERFLOW DRAIN LINE

ALWAYS RUN AN OVERFLOW DRAIN LINE.  IF NOT POSSIBLE TO

ROUTE  OVERFLOW  DRAIN  LINE,  INSTALL  LOW  VOLTAGE

OVERFLOW  SWITCH  KIT.  WIRE  KIT  TO  SHUT  DOWN

COMPRESSOR PER INSTRUCTIONS.

NO

YES

CLEAN OUT

VENT

PRESS IN

(DO NOT GLUE)

VENT MUST EXTEND

ABOVE HEIGHT OF

COIL DRAIN PAN BY

TWO INCHES (51 MM)

1” X 3/4” X 3/4”

REDUCING

TEE WITH

PLUG

PVC SCH 40 P- OR

J-TRAP 3/4”

OVERFLOW

DRAIN

OPTIONAL

SAFETY

PAN

FURNACE DRAIN PAN

WHEN A COIL IS LOCATED ABOVE A FINISHED SPACE, A 3/4” (19.1 MM) SECONDARY DRAIN

LINE MUST BE:

CONNECTED TO SECONDARY DRAIN PAN
OR
CONNECTED TO THE OVERFLOW DRAIN OUTLET OF THE FURNACE DRAIN PAN.

TRAPS  MUST  BE  DEEP  ENOUGH  TO  OFFSET  MAXIMUM  STATIC  DIFFERENCES  —

GENERALLY, TWO INCHES (51 MM).

DRAIN  LINE  SHOULD

SLOPE A MINIMUM OF

ONE  INCH  PER  10

FEET  (25 MM  PER  3

METERS)

NOTE 

— WHEN A FURNACE IS LOCATED ABOVE A FINISHED SPACE, THE SECONDARY DRAIN

PAN MUST HAVE A LARGER FOOTPRINT THAN THE FURNACE .

MAIN

DRAIN

TO APPROVED

DRAIN

FOR  NEGATIVE  PRESSURE  COILS  (BLOWER

AFTER COIL) TRAPS ARE REQUIRED ON ALL

DRAIN LINES CONNECTED TO COIL.

COMPACT OVERFLOW SWITCH WITH 3/4” FEMALE SLIP INLET

AND  MALE  ADAPTER,  TWO-PART  DESIGN  FOR  USE  WHERE

OBSTRUCTIONS PREVENT DIRECT THREADING

SECONDARY

DRAIN PAN

2”

(51 MM)

TRAP DEPTH

 Page 9

mrcool.com

Содержание MCDP Series

Страница 1: ...t for future reference Due to updates and constantly improving performance the information and instructions within this manual are subject to change without notice Please visit www mrcool com documentation to ensure you have the latest version of this manual Version Date 05 24 21 Installation Manual ...

Страница 2: ...vice agency As with any mechanical equipment contact with sharp sheet metal edges can result in personal injury Take care while handling this equipment and wear gloves and protective clothing The Clean Air Act of 1990 bans the intentional venting of refrigerant CFCs HCFCs and HFCs as of July 1 1992 Approved methods of recovery recycling or reclaiming must be followed Fines and or incarceration may...

Страница 3: ... 3 8 9 5 3 8 9 5 3 8 9 5 3 8 9 5 3 8 9 5 Number of rows 2 3 3 3 3 Fins per in m 18 709 12 472 12 472 12 472 12 472 lbs kg 1 package 44 20 44 20 49 22 57 26 58 26 MCDP 48B Nominal size tons 2 5 3 4 4 4 5 5 Suction vapor o d sweat 7 8 22 2 7 8 22 2 7 8 22 2 7 8 22 2 7 8 22 2 Liquid o d sweat 3 8 9 5 3 8 9 5 3 8 9 5 3 8 9 5 3 8 9 5 Condensate drain fpt 2 3 4 19 2 3 4 19 2 3 4 19 2 3 4 19 2 3 4 19 Net...

Страница 4: ...1 4 311 3 1 2 89 17 3 16 437 2 1 4 57 23 1 2 597 1 2 13 2 51 A B C D E G F 1 25 1 25 1 3 32 28 26 1 8 664 1 25 1 15 16 49 23 3 16 589 Outlet Opening Inlet Opening CONDENSATE DRAIN Outlet Opening Inlet Opening AIR FLOW SIDE VIEW FRONT VIEW LIQUID LINE MCDP 18 30 36 48 SUCTION Vapor LINE MCDP 24 60 1 2 13 22 5 8 575 H H SUCTION Vapor LINE MCDP 18 30 36 48 LIQUID LINE MCDP 24 60 Liquid and Suction Li...

Страница 5: ...nings Match 14 1 8 359 14 1 8 359 16 1 8 410 Physical Match MCDP 24B MCDP 30 36B 14 1 8 359 16 1 8 410 17 1 2 446 B Width Furnaces WARNING Coil Cabinet Wider Than Furnace Cabinet Supply Air Openings Match MCDP 48B 20 508 6 4 4 2 1 7 1 6 4 4 2 1 7 1 21 533 Coil opening will physically match the furnace supply air opening with the same letter designation in the model number Downflow Gas Furnaces MCDP...

Страница 6: ...Physical Match 24 1 2 622 D Width Furnaces 24 1 2 622 21 533 24 1 2 622 33 838 new models 40 1016 older models 33 838 new models 40 1016 older models C D 30 36 A N P A P C Coil Airflow D Downflow Capacity MBTU H Coil Dimension A 14 5 in B 17 5 in C 21 in D 24 5 in M M MRCOOL Page 5 mrcool com A 2nd Gen Refrigerant Case C Unpainted U Uncased P Painted Metering Device O Orifice T TXV C Capillary P P...

Страница 7: ...d to the plenum If the furnace and coil cabinet are the same size skip to step 3 Front to Rear 18A 24A 24B 30 36A 30 36B 14 1 4 394 mm 23 584 mm 30 36C 48B 48C 19 483 mm 50 60C 60D 22 1 2 571 mm Do not install screws through the drain pan 2 Install the provided coil locator brackets on the coil Align the coil locator brackets with the rear and sides of the coil cabinet Figure 2 illustrates how the...

Страница 8: ...Apply a small amount of refrigerant oil on the O ring 3 The suction line service port has no core Make sure that the service port cap is tightened securely 4 Insulate the refrigerant lines at the connections to prevent sweating of the suction line and seal cabinet opening All piping metering devices and connections must be insulated to prevent moisture damage caused by sweating To install the chec...

Страница 9: ...RIES UNITS USE NITROGEN OR DRY AIR AS A HOLDING CHARGE IF THERE IS NO PRESSURE WHEN THE RUBBER PLUGS ARE REMOVED CHECK THE COIL FOR LEAKS BEFORE INSTALLING REFER TO INSTRUCTIONS PROVIDED WITH OUTDOOR UNIT FOR LEAK TESTING EVACUATING AND CHARGING PROCEDURES FLOW REGULATED NITROGEN AT 1 TO 2 PSIG THROUGH THE REFRIGERATION GAUGE SET INTO THE VALVE STEM PORT CONNECTION ON THE OUTDOOR UNIT LIQUID LINE ...

Страница 10: ...E INSTALL LOW VOLTAGE OVERFLOW SWITCH KIT WIRE KIT TO SHUT DOWN COMPRESSOR PER INSTRUCTIONS NO YES CLEAN OUT VENT PRESS IN DO NOT GLUE VENT MUST EXTEND ABOVE HEIGHT OF COIL DRAIN PAN BY TWO INCHES 51 MM 1 X 3 4 X 3 4 REDUCING TEE WITH PLUG PVC SCH 40 P OR J TRAP 3 4 OVERFLOW DRAIN OPTIONAL SAFETY PAN FURNACE DRAIN PAN WHEN A COIL IS LOCATED ABOVE A FINISHED SPACE A 3 4 19 1 MM SECONDARY DRAIN LINE...

Страница 11: ... oils and greases which generally are not present on most installations Do not use alkaline washes to dissolve oxides such as zinc oxide aluminum oxide and iron oxide rust These three oxides are more corrosion resistant than base metals Dissolving or removing them will cause an increase in corrosion cleaning requires the use of acidic or alkaline cleaners cleaner from all equipment components Be c...

Страница 12: ...9 38 94 1300 614 43 107 1300 614 47 117 1200 565 54 135 1200 566 43 107 1400 661 49 122 1400 661 05 12 525 245 05 12 410 194 06 15 600 285 07 17 600 283 08 19 660 310 08 19 495 233 08 20 700 330 10 25 700 330 10 25 795 375 10 25 580 273 10 25 800 380 13 32 800 378 15 37 980 465 15 37 785 371 13 32 900 425 17 42 900 425 20 50 1165 550 20 50 995 469 16 40 1000 470 21 52 1000 472 25 62 1320 625 25 62...

Страница 13: ...750 825 28 70 1745 824 25 62 1750 825 28 70 1745 824 27 67 1805 850 31 77 1800 850 27 67 1805 850 31 77 1800 850 28 70 1845 870 32 80 1850 874 28 70 1845 870 32 80 1850 874 29 72 1905 900 33 82 1890 892 29 72 1905 900 33 82 1890 892 30 75 1950 920 34 85 1950 920 30 75 1950 920 34 85 1950 920 32 80 2000 945 36 90 2000 944 32 80 2000 945 36 90 2000 944 33 82 2055 970 38 95 2050 968 33 82 2055 970 38...

Страница 14: ...Signature Series Please read this manual carefully before installation and keep it for future reference Consult with the sales agency or manufacturer for details ...

Отзывы: