Calibrating the Main Temperature Control (OFFSET) 

 

 

1. Press  

  several times scroll to the parameter PASS. Set the PASS value to1000 

2. Press and hold the   

  key until the setup   

  Menu page is obtained. Then, press   

  key to scroll to the parameter.   

 

3. Press

  key several times to scroll to the parameter OFTL to calibration low 

value. Send your low signal to the sensor input of the controller, then press and 

release the

  key. If the process value (the upper display) is different from the 

input signal, the user can use     and 

  to change the OFTL value (the lower 

display) until the process value is equal to the value the user needs. Press and hold 

the 

key for 5 seconds to complete the low point calibration. A similar procedure 

is applied for high scale calibration. 

 

The two points OFTL and OFTH construct a straight line. For the purpose of 
accuracy, it is best to change the value same on the two points as possible. 

 

 

 

 