3 Product description
Maschinenfabrik Reinhausen GmbH 2015
32
4349315/00 EN
VACUTAP® VR®
Figure 13: RS 2001
1 Gasket
7 Cable connection
2 Grounding cable
8 Protective cover
3 Terminal box cover
9 Dummy plug
4 OPERATION (reset) test button
10 Connection terminals
5 Slotted screw
11 Cylinder head screw for protec-
tive conductor connection
6 OFF (test tripping) test button
The protective relay RS 2003 and RS 2004 has a 1/2"-14NPT adapter in
place of the cable connection (position 7).
Pressure monitoring device DW
Function description
The DW 2000 pressure-operated relay protects the on-load tap-changer
from unacceptable pressure increases, contributing to the safety of the
transformer. The pressure-operated relay is installed on the outside of the
on-load tap-changer and is tripped by unacceptable static and dynamic pres-
sures in the on-load tap-changer oil vessel.
View from above
3.5
3.5.1