1 Safety
2 Product specification
3 Assembly, preparation and evaluation
1
Safety
1.1 Safety instructions
All personnel involved in operation of this equipment must:
- be suitably qualified and
- strictly observe these operating instructions.
Improper operation or misuse can lead to
- serious or fatal injury,
- damage to the equipment and other property of the user
- a reduction in the efficiency of the equipment.
Safety instructions in this manual are presented in three
different forms to emphasize important information.
WARNING
This information indicates particular danger to life and
health. Disregarding such a warning can lead to serious
or fatal injury.
CAUTION
This information indicates particular danger to the
equipment or other property of the user. Serious or
fatal injury cannot be excluded.
NOTE
These notes give important information on a certain
issue.
2
Product description
The MESSKO® Gas Quick Test is used to test the gases in the
MESSKO® gas sampler or the Buchholz relay for the presence
of carbon monoxide and hydrogen. No quantitative analysis
of the gases is made.
2.1 Mode of operation
A Y-connector is screwed onto the gas withdrawal valve for
qualitative analysis of the gases in the gas sampler or in the
Buchholz relay. The Y-connector holds two detector tubes for
testing the presence of carbon monoxide and the presence
of hydrogen respectively. After opening the gas withdrawal
valve, the gas contained is routed at an appropriate pressure
(> 0.5 bar) to the outside through the detector tubes and
leads where applicable to their discolouration.
3 Assembly, preparation and evaluation
3.1 Gas sampler
Gas withdrawal in accordance with BA 3178923 MESSKO®
Gas sampler, section 4.2, has been carried out in preparation
or is still to be carried out!
(1) Unscrew the sealing cap (Fig. 1/1) from the gas withdra-
wal valve (Fig. 1/4).
(2) Screw the Y-connector (Fig. 1/2) onto the gas withdra-
wal valve (Fig. 1/4) and check if the connector is tightened
properly.
(3) Cut open the detector tubes for the carbon monoxide
and hydrogen analysis on both sides using the tube cutter
1.2 Specified application
The MESSKO® Gas Quick Test is used to test the gases in the
MESSKO® gas sampler or the MESSKO® Buchholz relay for
the presence of carbon monoxide and hydrogen.
1.3 Important notes on equipment operation
The user is advised to strictly comply with the national acci-
dent prevention regulations.
It is especially emphasized that work on active or live compo-
nents is only permissible while these components are either
de-energized or protected against direct contact.
Installation is subject to the relevant national safety regu-
lations.
WARNING
All relevant fire protection regulations and specifications
for handling toxic and flammable gases must be strictly
observed.
CAUTION
The MESSKO® Gas-Quick Test may only be carried out by
qualified, skilled personnel and only in accordance with
these instructions.
It is the responsibility of the user to make sure that the
test set is used for the specified application only.
For safety reasons, any unauthorized and improperly
executed usage of the test set, are forbidden without
first consulting Messko!
CAUTION
Danger of glass breakage!