14 Appendix
119
BA6820378-03 EN
No.
Value
Designation
DB100/200/200D DB200G
16
ON/
OFF
Right cylinder closed
No
Yes
17
ON/
OFF
Left regeneration
Yes
Yes
18
ON/
OFF
Right regeneration
DB200D only
Yes
19
ON/
OFF
Left sensor status
Yes
Yes
20
ON/
OFF
Right sensor status
DB200D only
Yes
Analog values (input register)
Function code "04" for reading the information
No.
MSW/
LSW*
Value
Designation
DB100/200/200D DB200G
0
MSW
float32
Left humidity sensor
Yes
Yes
1
LSW
2
MSW
float32
Left temperature sen-
sor
Yes
Yes
3
LSW
4
MSW
float32
Right humidity sensor
DB200D only
Yes
5
LSW
6
MSW
float32
Right temperature sen-
sor
DB200D only
Yes
7
LSW
*) MSW=most significant word; LSW=least significant word