6 Mounting
Maschinenfabrik Reinhausen GmbH 2020
62
4453918/14 EN
ETOS
®
TD
6.4.4 MSENSE®-FO ECU-I/S
If you would like to use an MSENSE®-FO ECU-I or ECU-S sensor, you must
connect the sensor to the RS485 plug terminals on the sensor bus. Use a
shielding clamp to apply the shield to the cable. If the MSENSE®-FO sensor
is the only bus device or the last bus device, you must use a terminating re-
sistor (120 Ω, 0.5 W). You must activate the half-duplex, 2-conductor operat-
ing mode on the sensor via the MSET-FO configuration software.
CPU-COM2
MSENSE®-FO
D0 (A)
D1 (B)
Com. (C)
1
2
3
4
5
6
7
8
9
Tx+ 1
2
3
4
5
Tx-
Rx+
Rx-
GND
Figure 47: Connection example MSENSE®-FO ECU-I and ECU-S (terminal RS485)
6.5 Information about connecting analog sensors
NOTICE
Damage to the device and sensors!
Incorrectly connected and configured analog inputs/outputs may result in
damage to the device and sensor.
► Follow information about connecting analog sensors [
62].
► Configure analog inputs and outputs according to the connected sensors.
Содержание ETOS TD
Страница 1: ...Motor drive unit ETOS TD Operating Instructions 4453918 14 EN ...
Страница 329: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 329 4453918 14 EN ETOS TD 15 2 2 Drawings 15 2 2 1 ETOS TD S ...
Страница 330: ......
Страница 331: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 331 4453918 14 EN ETOS TD 15 2 2 2 ETOS TD L ...
Страница 332: ......
Страница 333: ...15 Technical data Maschinenfabrik Reinhausen GmbH 2020 333 4453918 14 EN ETOS TD 15 2 2 3 ETOS TD XL ...
Страница 334: ......
Страница 355: ......