8 Operation
Maschinenfabrik Reinhausen GmbH 2018
123
5252433/02 EN
ECOTAP
®
VPD
®
CONTROL PRO
IP address
You can use this parameter to assign an IP address to the device.
To set the IP address, proceed as follows:
Assign IP addresses to both web-based visualization and SCADA (optional)
in different subnets. Otherwise you will not be able to establish a connec-
tion.
1. Go to
Settings > Parameters > IEC
60870-5-104 > IP address
.
2. Enter the IP address.
3. Press the
Accept
button to save the modified parameter.
Subnet mask
You can use this parameter to set the subnet mask.
Be sure to enter a valid network mask that is not 0.0.0.0, otherwise it will not
be possible to connect to the device.
To set the subnet mask, proceed as follows:
1. Go to
Settings > Parameters > IEC
60870-5-104 > Subnet mask
.
2. Enter the subnet mask.
3. Press the
Accept
button to save the modified parameter.
Gateway address
You can use this parameter to set the gateway's IP address.
If you set the value to 0.0.0.0, no gateway is used.
To set the gateway address, proceed as follows:
1. Go to
Settings > Parameters > IEC
60870-5-104 > Gateway address
.
2. Enter the gateway address.
3. Press the
Accept
button to save the modified parameter.
TCP port
You can use this parameter to set the TCP port.
To set the TCP port, proceed as follows:
1. Go to
Settings > Parameters > IEC
60870-5-104 > TCP port
.
2. Enter the TCP port.