PAGE 44 — DCA40SSKU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #0 (07/20/17)
E N G I N E B L O C K H E AT I N G E L E M E N T
ANDINTERNAL BATTERY CHARGER 120 VAC
INPUT RECEPTACLES (OPTIONAL)
This generator can be equipped as an
option
with a
engine block heating element
and an
internal battery
charger
. They are provided with electric cords to connect
to a commercial power source.
The engine block heating element and internal battery
charger both require 120 VAC in order to operate. A
receptacle (Figure 65 )has been provided on the output
terminal panel to allow commercial power to be applied.
These units will
ONLY
function when commercial power
has been supplied to them. When using extension cords,
refer to Table 6 for the correct size and length.
The battery charger should always be connected to a
commercial power source to ensure that the battery does
not get discharged.
When using the generator in
hot
climates there is no
need to apply power to jacket water heater. However, if the
generator will be used in
cold
climates, it is best to apply
power to the jacket water heater at all times.
If the generator will be used daily, the battery should
normally not require charging. If the generator will be idle
(not used) for long periods of time, apply power to the
battery charger receptacle via commercial power using a
power cord of adequate size.
GENERATOR STORAGE
For long term storage of the generator the following is
recommended:
Drain the fuel tank completely. Treat with a fuel stabilizer
if necessary.
Completely drain the oil from the crankcase and refill if
necessary with fresh oil.
Clean the entire generator, internal and external.
Cover the generating set and store in a clean, dry place.
Disconnect the battery.
Make sure engine coolant is at proper level.
If generator is mounted on a trailer, jack trailer up and
place on blocks so tires do not touch the ground or block
and completely remove the tires.
NOTICE
To ensure adequate starting capability, always have
power applied to the generator's internal battery
charger.
MAINTENANCE
Figure 65. Battery Charger and Jacket Water
Heater (Option)
BATTERY CHARGER
BATTERY CHARGER/
ENGINE BLOCK
HEATING ELEMENT
120 VAC INPUT
RECEPTACLE
OUTPUT TERMINAL
PANEL ASSEMBLY
ENGINE BLOCK
HEATING ELEMENT
DC
AM
PE
RE
S
TO STARTER “B”
TERMINAL
RED 16 AWG.
TO CHASSIS
GROUND
GREEN 16 AWG.