PAGE 54 — DCA1100SSC 60 HZ GENERATOR • OPERATION MANUAL — REV. #1 (01/17/18)
2. Next, remove the two screws that secure the engine
control panel door to the generator frame (Figure 68).
Figure 68. Engine Control Panel Door
3. Open the engine control panel door to gain access to
the diagnostic guage.
4. Secure panel door with latch.
5. When the engine is not running,
PUSH and HOLD
the
fuel check button
and at the same time place the
ECU Auto Start/Stop Switch in the
MANUAL
position.
6.
PRESS the
menu key
to display the main menu. Use
the arrow keys to scroll through the main menu until
the "Stored Codes" parameter is highlighted.
7. Once the "Stored Codes" parameter is highlighted,
PRESS the
enter key
to view the stored codes.
Figure 69 is a typical example of a high temperature
code.
Low Oil Pressre
High temp.
Over Crank
Over Speed
Engine Started
ECU Intergrated Gauge Control
R
ECU CONTROLLER
AUTO
MANUAL
OFF/RESET
FUEL LEVEL
PRE-ALARM
SHUTDOWN
ENGINE SPEED
HIGH
LOW
PREHEAT LAMP
PREHEAT BUTTON
EMERGENCY STOP BUTTON
FUEL METER
CHECK BUTTON
REMOVE
REMOVE
DIAGNOSTIC GAUGE IS
LOCATED BEHIND ENGINE
CONTROL PANEL DOOR.
Figure 69. High Temperature Code Example
8. After performing the diagnostic test, place the ECU
Auto Start/Stop Switch in the
OFF
position.
9. For more detail information regarding engine diagnostic
trouble codes reference the Cummins engine
operator's manual.
RESTARTING GENERATOR
1. Make sure all engine faults have been corrected before
restarting the generator.
2.
PUSH the reset button (Figure 70) on the diagnostic
panel for at least 1 second to clear the display.
Figure 70. Reset Button
3. Place the ECU Auto Start/Stop Switch in the desired
position (Auto or Manual).
4. Restart generator as outlined in the Operation Section
of this mamual.
1 OF X
WARNING
ENG
SPN110
COOL TEMP
MORE
HIGH
FM100
HIDE
RESET
DIAGNOSTIC DISPLAY