16
10
Operation Logic
Automatically (default)
If selected and utility is available,
inverter will work in line mode.
Once
utility
frequency
is
unstable, inverter will work in
bypass mode if bypass function
is not forbidden in program 23.
Online mode
If selected, inverter will work in
line mode when utility is
available.
ECO Mode
If selected and bypass is not
forbidden in program 23, inverter
will work in ECO mode when
utility is available.
11
Maximum utility charging
current
Note: If setting value in
program 02 is smaller than
that in program in 11, the
inverter will apply charging
current from program 02 for
utility charger.
2A
10A
20A
30A (default)
40A
50A
60A
12
Setting voltage point back
to utility source when
selecting “SBU” (SBU
priority) or “SUB” (Solar
first) in program 01
3KW default setting: 23.0V
5KW default setting: 46.0V