Smoke damper

rev 21-10

Electric cables and system

For Manual Activation version (MA), the electric cables and system must be protected and designed to 
have at least 30 minutes circuit integrity.

Operation

All smoke dampers have a electrical actuator. They are designed to be installed indoor in a smoke evacua-
tion and reversable HVAC system.

Before starting the system it is necessary to check the system for damages and that it is consistent to the 
fire expert design.

Checking and Maintenance

Following features shall be checked up during a revision of the damper at least once every six months:
• 

All parts are to be installed according to this mounting instruction.

• 

The damper must not be damaged in any way, the cross-section of the casing, the motor and the 
covering box of the motor must not be damaged in any way.

• 

All connections with the smoke evacuation system are to be tightened and properly connected. 

• 

The ducts connected to the damper must be suspended or supported in order to bear the damper’s 
weight too.

• 

There must not be any flammable bodies on the damper surface and 50 mm away from the system 
itself.

Periodic inspection and cleaning

Periodic inspection shall be performed in accordance with the requirements of the law or by the building 

regulations or other local regulations.

In the absence of specific regulations (or to their complement), in accordance with point 8.3 of the EN 

12101-8 standard, it is recommended to carry out the following controlactivities at intervals of no more 

than 6 months: execute an opening and closing test and check the correct movement of the blade and the 

correct functioning of the microswitches (limit switches). Blade opening time shall be not more than 60 

seconds. Blade closing time shall be not more than 60 seconds.

Together with the control activities, it is recommended to visually verify the absence of corrosion, the 

integrity of the electrical wiring and the sealing of the construction support. Damper cleaning is included 

in the ordinary maintenance activities of the ventilation ducts. Smoke control dampers can be cleaned 

with a dry or wet cloth. In the case of resistant dirt, it is possible to use normal household detergents. If 

prescribed for the type of building, it is possible to use disinfectant detergents. The use of detergents or 

mechanical abrasive cleaning systems is not permitted. These indications comply with the standards EN 

12101-8 annex B and EN 15423 annex C.

Содержание WXH Series

Страница 1: ...CIRCULAR SERIES WXH 1500Pa Cert N 1812 CPR 1189 Technical Manual English WXH SINGLE COMPARTMENT SMOKE CONTROL DAMPER ...

Страница 2: ...ng to EN1366 10 and classified according to EN13501 4 The damper is suitable for vertical and horizontal installation in single compartment smoke duct evacuation systems with maximum temperature of 600 C for 2 hours with smoke leakage class S at 1500Pa negative pressure Declaration of performance The damper is CE marked with the declaration of performance according to EN12101 8 as a circular smoke...

Страница 3: ... installation both horizontal and vertical and with blade rotation axis both horizontal and vertical The fire classification obtained according to EN13501 4 2016 is According to the classification obtained according to Tables 1 and 3 level 3 and according to paragraph 6 3 2 2 of EN1366 10 2011 A1 2017 it is allowed to use single compartment smoke control dampers WXH In single compartment smoke exh...

Страница 4: ... 115 298 9 5 407 12 0 560 115 298 11 0 407 13 5 630 115 298 12 5 407 15 Classification details E600 120 ved hod i S 1500Pa C10000 AA single E integrity Temperature Time ved Installation on duct penetrating a vertical wall hod Installation on duct penetrating a horizontal wall origin of fire is irrelevant Smoke leakage 5 m3 h m2 Maximum negative pressure Motor cycles use in combined smoke control a...

Страница 5: ...et immediately Storage The goods should be stored inside and protected to prevent dust debris and humidity to damage the goods Before mounting Before starting the mounting of the damper it is necessary to inspect all components to make sure that they are correct according to the project documentation and to make sure they have not been damaged during transport or storage When handling the products...

Страница 6: ...5 mm to support itself weight and to prevent damage to the gasket The damper must be installed on certifi ed and CE marked smoke control system Ø nom Minimum number of fasteners required to achieve sufficient strength 100 630 4 Mounting Technical data for the motors BLE motor BLE24 BLE230 Power supply AC DC 19 2 28 8 V 50 60 Hz AC 198 264 V 50 60 Hz Power consumption 7 5 W 5 W For wire sizing 9 VA...

Страница 7: ...of several actuators possible Power consumption and switching thresholds must be observed 2 wire open close control The actuator is overload proof and can thus remain energized even at the end stops Two microswitches with fixed settings are installed in the actuator for indicating the damper end positions The position of the damper blade can be read off on a mechanism position indicator The crank ...

Страница 8: ... Periodic inspection and cleaning Periodic inspection shall be performed in accordance with the requirements of the law or by the building regulations or other local regulations In the absence of specific regulations or to their complement in accordance with point 8 3 of the EN 12101 8 standard it is recommended to carry out the following controlactivities at intervals of no more than 6 months exe...

Страница 9: ...k that the smoke control damper is in the normal operating position Keep records of all inspections repair activities any problems encountered and their resolution This practice even when not mandatory is very useful in practice Disposal Disposal must be carried out in accordance with national legislation For electrical and electronic parts also refer to EU Directive 2011 65 Type WXH Circular smok...

Отзывы:

Похожие инструкции для WXH Series