Smoke damper

rev 21-10

Preparations:

• 

Cut ducts at right angles.

• 

Carefully remove any burrs from cut edges. Installation is 
easier and the risk of damaging the gasket is reduced if there 
are no burrs.

• 

Cut away the needles created from the fold.

Assembly

• 

Start by inserting the turned-over edge of the damper into 
the duct.

• 

Check that the fi rst lip of the gasket is in contact with the 
edge of the duct all the way around and sticks straight out so 
that the lip is not twisted in one direction or the other.

• 

Push the end of the damper into the duct. Twisting the 
damper slightly aids insertion.

• 

Secure the damper in the duct using self-tapping screws 
Ø4,2×13.

• 

Fasteners should be positioned on the duct close the damper 
(minimum 10-15 mm) to support itself weight and to prevent 
damage to the gasket. 

• 

The damper must be installed on certifi ed and CE marked 
smoke control system.

Ø

nom

Minimum number 

of fasteners

required to achieve

sufficient strength.

100-630

4

Mounting

Technical data for the motors

BLE motor

BLE24

BLE230

Power supply....................................

AC/DC 19.2 28,8 V,  

50/60 Hz

AC 198-264 V,  

50/60 Hz

Power consumption..........................

7,5 W

5 W

For wire sizing...................................

9 VA

12 VA

Connection........................................

Cable 1 m, 3×0,75 mm

2

Cable 1 m, 3×0,75 mm

2

Operative angle................................

Max. 90°

Max 105°

Torque at rated voltage.....................

Min. 15 Nm

Min. 15 Nm

Direction of rotation..........................

Selected by mounting L/R

Selected by mounting L/R

Position indication............................

Mechanical with pointer

Mechanical with pointer

Running time....................................

<30 s for 90°

<30 s for 90°

Sound power level...........................

Max. 62 dB (A)

Max. 62 dB (A)

Protection class................................

III Safety extra-low voltage II totally insulated

Protection type.................................

IP 54

IP54

Ambient temperature range..............

-30 to +50°C

-40 to + 80°C

Ambient moisture..............................

95 % RH

95 % RH

Содержание WXH Series

Страница 1: ...CIRCULAR SERIES WXH 1500Pa Cert N 1812 CPR 1189 Technical Manual English WXH SINGLE COMPARTMENT SMOKE CONTROL DAMPER ...

Страница 2: ...ng to EN1366 10 and classified according to EN13501 4 The damper is suitable for vertical and horizontal installation in single compartment smoke duct evacuation systems with maximum temperature of 600 C for 2 hours with smoke leakage class S at 1500Pa negative pressure Declaration of performance The damper is CE marked with the declaration of performance according to EN12101 8 as a circular smoke...

Страница 3: ... installation both horizontal and vertical and with blade rotation axis both horizontal and vertical The fire classification obtained according to EN13501 4 2016 is According to the classification obtained according to Tables 1 and 3 level 3 and according to paragraph 6 3 2 2 of EN1366 10 2011 A1 2017 it is allowed to use single compartment smoke control dampers WXH In single compartment smoke exh...

Страница 4: ... 115 298 9 5 407 12 0 560 115 298 11 0 407 13 5 630 115 298 12 5 407 15 Classification details E600 120 ved hod i S 1500Pa C10000 AA single E integrity Temperature Time ved Installation on duct penetrating a vertical wall hod Installation on duct penetrating a horizontal wall origin of fire is irrelevant Smoke leakage 5 m3 h m2 Maximum negative pressure Motor cycles use in combined smoke control a...

Страница 5: ...et immediately Storage The goods should be stored inside and protected to prevent dust debris and humidity to damage the goods Before mounting Before starting the mounting of the damper it is necessary to inspect all components to make sure that they are correct according to the project documentation and to make sure they have not been damaged during transport or storage When handling the products...

Страница 6: ...5 mm to support itself weight and to prevent damage to the gasket The damper must be installed on certifi ed and CE marked smoke control system Ø nom Minimum number of fasteners required to achieve sufficient strength 100 630 4 Mounting Technical data for the motors BLE motor BLE24 BLE230 Power supply AC DC 19 2 28 8 V 50 60 Hz AC 198 264 V 50 60 Hz Power consumption 7 5 W 5 W For wire sizing 9 VA...

Страница 7: ...of several actuators possible Power consumption and switching thresholds must be observed 2 wire open close control The actuator is overload proof and can thus remain energized even at the end stops Two microswitches with fixed settings are installed in the actuator for indicating the damper end positions The position of the damper blade can be read off on a mechanism position indicator The crank ...

Страница 8: ... Periodic inspection and cleaning Periodic inspection shall be performed in accordance with the requirements of the law or by the building regulations or other local regulations In the absence of specific regulations or to their complement in accordance with point 8 3 of the EN 12101 8 standard it is recommended to carry out the following controlactivities at intervals of no more than 6 months exe...

Страница 9: ...k that the smoke control damper is in the normal operating position Keep records of all inspections repair activities any problems encountered and their resolution This practice even when not mandatory is very useful in practice Disposal Disposal must be carried out in accordance with national legislation For electrical and electronic parts also refer to EU Directive 2011 65 Type WXH Circular smok...

Отзывы: