Switching off (blade closing):
Manual: Push the off button.
Automatic: When the temperature in the duct exceeds 70°, the thermal fuse melts and the blade closes.
Resetting:
Manual resetting: Turn the lever anti-clockwise.
Options:
• S2 : End and start position contacts (micro switches). On the S1-25 electronic card, connect the NC / NO / C for the start
contact (DCU) and the NC / NO / C for the end contact (FCU). See electrical connections paragraph for further details.
WK25 M:
Remote controlled mechanism with thermal fuse.
Switching off (blade closing):
Manual: Push the off button.
Automatic: When the temperature in the duct exceeds 70°, the thermal fuse melts and the blade closes.
Remote control: with power supply (input magnet) or power supply interruption (interruption magnet). (Automatic 24/48V DC
electromagnetic coil).
Resetting:
Manual resetting: Turn the lever anti-clockwise.
Note:
For this remote control version, the S2 micro switches are fitted as standard.
WK25 IN MOTORIZED VERSION V / D:
Note:
For the motorized version micro switch is standard.
Siemens servo-driven model
To manually open the damper use the provided key to rotate clockwise until the
indicator reaches a value of 90° and with a screw driver rotate the screw shown
in the figure anti-clockwise.
To manually close the damper insert the supplied key in the hole and rotate it
anti-clockwise until the damper is completely closed.
To automatically close the damper, if there is power, press the button located on
the temperature sensor, or turn off the power.
Automatic closing is also performed by the 72ºC thermal fuse.
Solid Air
®
Luchtverdeeltechniek BV Telefoon (020) 696 69 95 Fax (020) 691 30 62 www.solid-air.nl Brandkleppen manual 06 2013
Solid Air
®
Solid Air
®
Luchtverdeeltechniek BV Telefoon (020) 696 69 95 Fax (020) 691 30 62 www.solid-air.nl Brandkleppen manual 06 2013
Solid Air
®
Luchtverdeeltechniek BV Telefoon (020) 696 69 95 Fax (020) 691 30 62 www.solid-air.nl 06 2013
Brandkleppen manual
WH25
WH45
WK25
WK45
Содержание Solid Air WK25 D
Страница 13: ...12 1MLWK25R0G 12 EC declaration of conformity ...