HOLES AND SEALING:
Attention: Make sure the damper and duct are correctly aligned.
The WK25 damper does not have a specific air passage direction.
Base and height dimensions indicated below refer to the nominal fire damper dimensions.
On 100 mm concrete floor
Floor hole dimension: B + 70mm, H + 70mm
On 150 mm concrete floor:
Floor hole dimension: B + 70mm, H + 70mm
On 100 mm concrete wall
Wall hole dimension:
B + 70mm, H + 70mm
Damper installation:
1. A rectangular hole sized (B + 70 mm) x (H + 70 mm) must be provided in the wall.
2. Place the fire damper inside the prepared hole.
3. Sealing with mortar class M10 or higher.
4. Set up a mechanism clearance and access area: 250mm.