Brandkleppen manual

WH25
WH45

WK25
WK45

Содержание Solid Air WK25 D

Страница 1: ...Brandkleppen manual Postbus 22756 1100 DG Amsterdam Z O Tel 31 0 20 696 69 95 Fax 31 0 20 691 30 62 mail solid air nl www solid air nl Solid Air Brandkleppen manual WH25 WH45 WK25 WK45 ...

Страница 2: ... l y www mp3 italia it MAINTENANCE AND USE MANUAL WK25 Rectangular fire damper with low pressure drop 500 Pa Solid Air Luchtverdeeltechniek BV Telefoon 020 696 69 95 Fax 020 691 30 62 www solid air nl Brandkleppen manual 06 2013 Brandkleppen manual WH25 WH45 WK25 WK45 ...

Страница 3: ...ism entirely outside wall Easy to install Maintenance free 2 RANGE OF DIMENSIONS Free area dm width 12 x height 37 10 000 with width and height in mm 4 3 2 5 6 1 7 1 Galvanised steel duct 2 Moveable blade in refractive material 3 Control mechanism 4 Connection flanges 5 Intumescent seal 6 Blade seal 7 Thermal fuse Solid Air Luchtverdeeltechniek BV Telefoon 020 696 69 95 Fax 020 691 30 62 www solid...

Страница 4: ...tomatically and remote controlled fire damper Rectangular cross section Mandatory Manual reset by direct action on the moveable part after closing when cold Manual reset by direct action on the moveable part after closing when cold Safety position contact limit switch DCU FCU S2 Motorized reset after closing when cold can be local or remote Safety position contact limit switch Safety options Safet...

Страница 5: ...mpliance with the technical specifications Use temperature 50 C maximum The WK25 fire damper is always tested in the frame of standardised supports in compliance with EN 1366 2 1999 table 3 4 5 The results obtained are valid for all similar support frames which have a thickness density and fire resistance equal or higher than that of the test Example of similar constructions aerated concrete wall ...

Страница 6: ...concrete wall Wall hole dimension B 70mm H 70mm Damper installation 1 A rectangular hole sized B 70 mm x H 70 mm must be provided in the wall 2 Place the fire damper inside the prepared hole 3 Sealing with mortar class M10 or higher 4 Set up a mechanism clearance and access area 250mm Solid Air Luchtverdeeltechniek BV Telefoon 020 696 69 95 Fax 020 691 30 62 www solid air nl Brandkleppen manual 06...

Страница 7: ... 5 mm on both sides to cover the rock wool On 70 mm light vertical modular plaster boards walls carreaux de plâtre Wall hole dimension B 50mm H 50mm Damper installation 1 A rectangular hole sized B 50 mm x H 50 mm must be provided in the wall 2 Position the damper in the hole on the wall 3 It is not necessary to insert any material simply cover the gap between wall and fire damper applying on both...

Страница 8: ... single damper 7 CONTROL MECHANISMS WK25 MANUAL VERSION B M 70 C thermal fuse Manual switch off possible Manual resetting use the box lever turn anti clockwise 1 Manual switch off button 2 Control lever in safety position 3 Manual resetting turn the lever in the direction of the arrow WK25 B Automatically controlled mechanism with thermal fuse Solid Air Solid Air Luchtverdeeltechniek BV Telefoon 0...

Страница 9: ...tic 24 48V DC electromagnetic coil Resetting Manual resetting Turn the lever anti clockwise Note For this remote control version the S2 micro switches are fitted as standard WK25 IN MOTORIZED VERSION V D Note For the motorized version micro switch is standard Siemens servo driven model To manually open the damper use the provided key to rotate clockwise until the indicator reaches a value of 90 an...

Страница 10: ...LWK25R0G 8 DIMENSIONS BLADE EXPOSURE Solid Air Solid Air Luchtverdeeltechniek BV Telefoon 020 696 69 95 Fax 020 691 30 62 www solid air nl Brandkleppen manual 06 2013 Brandkleppen manual WH25 WH45 WK25 WK45 ...

Страница 11: ... of the damper to the mains must only be done by a qualified electrician DCU single pole beginning of stroke contact C common NC normally closed lectronic mother board S0 25 for coil power supply and micro switches DCU single pole beginning of stroke contact NC normally closed NO normally open Coil power connector inal block for start and end contacts 10 mains must only be done by a qualified elec...

Страница 12: ...ation 3 5 W In st by 2 W Input magnet P 3 4 W Motor 230V AC WK25 D Siemens GNA326 1ET In operation 4 5 W In st by 3 5 W Positioning contacts Standard 1mA 1A DC 5V AC 48V Standard 1mA 0 500mA DC 5V AC 48V Blade closing time Spring 1 s Motor 30 s Protection IP42 IP54 11 MAINTENANCE No special maintenance required Have the damper checked at least once a year After each intervention have the dust clea...

Страница 13: ...12 1MLWK25R0G 12 EC declaration of conformity ...