Read and Follow These Guidelines 

 

Use separate paths to route wiring for power and devices. If power 
wiring and device wiring paths must cross, make sure the wires are 
perpendicular at the intersection point. 

NOTE 

Do not run signal or communications wiring and power wiring in 
the same wire conduit. To avoid interference, wires with different 
signal characteristics should be routed separately. 

 

 

 

You can use the type of signal transmitted through a wire to 
determine which wires should be kept separate. The rule of thumb is 
that wiring with similar electrical characteristics can be bundled 
together. 

 

Keep input wiring and output wiring separate. 

 

It is strongly advised that you label wiring to all devices in the system 
when necessary. 

 

 

ATTENTION 

This product is intended to be supplied by a Listed Power Unit 
marked “Class 2” or “LPS” and rated O/P: 9.6 W (12 V/0.78 A to 
48 V/0.2 A). 

 

 

 

ATTENTION 

Make sure that the external power adapter (includes power cords 
and plug assemblies) provided with the unit is certified and 
suitable for use in your country. 

 

Grounding the Moxa OnCell G3150A-LTE 

Grounding and wire routing help limit the effects of noise due to 
electromagnetic interference (EMI). Run the ground connection from the 
ground screw to the grounding surface prior to connecting devices. The 
minimum cross-sectional area of the grounding conductor should be 
equal to that of the input cable. 

 

ATTENTION 

This product is intended to be mounted on a well-grounded 
mounting surface, such as a metal panel. The potential difference 
between the two ground potentials must be zero. If the potential 
difference is NOT zero, the product could be permanently 
damaged. 

 

Содержание OnCell G3150A-LTE

Страница 1: ...31500023 1802031500023 OnCell G3150A LTE Series Quick Installation Guide Moxa OnCell Series Version 2 1 January 2021 Technical Support Contact Information www moxa com support 2021 Moxa Inc All rights...

Страница 2: ...allation and Configuration Before installing the OnCell G3150A LTE make sure that all items in the package checklist are in the box In addition you will need access to a notebook computer or PC equipp...

Страница 3: ...55 255 255 0 you should set the IP address of the computer to 192 168 127 xxx and subnet mask to 255 255 255 0 Step 4 Use the web based manager to configure the OnCell G3150A LTE Open your computer s...

Страница 4: ...l block top down PWR1 and PWR2 1 digital relay and 2 digital inputs 3 Grounding screw M5 4 2x2 MIMO antenna ports for LTE female SMA 5 RS 232 serial console RJ45 6 10 100 Base T X Ethernet port RJ45 7...

Страница 5: ...nting DIN Rail Kit Dimensions Unit mm inch The OnCell G3150A LTE Series computers come with a DIN rail kit attached to the back panel Mount the OnCell G3150A LTE Series on corrosion free mounting rail...

Страница 6: ...OnCell G3150A LTE from the DIN rail reverse steps 1 and 2 above Wall Mounting optional Wall Mounting Kit Dimensions Unit mm inch For some applications it may be more convenient to mount the OnCell G3...

Страница 7: ...diagram Tighten the four screws for added stability WARNING This equipment is intended to be used in a Restricted Access Location such as a dedicated computer room where access can only be gained by...

Страница 8: ...n necessary ATTENTION This product is intended to be supplied by a Listed Power Unit marked Class 2 or LPS and rated O P 9 6 W 12 V 0 78 A to 48 V 0 2 A ATTENTION Make sure that the external power ada...

Страница 9: ...screwdriver to tighten the wire clamp screws on the front of the terminal block connector STEP 3 Insert the plastic terminal block connector prongs into the terminal block receptor which is located on...

Страница 10: ...n below MDI Port Pinouts MDI X Port Pinouts 8 pin RJ45 Pin Signal Pin Signal 1 Tx 1 Rx 2 Tx 2 Rx 3 Rx 3 Tx 6 Rx 6 Tx Serial DB9 Connection The OnCell G3150A LTE has one DB9 male port that supports RS...

Страница 11: ...cellular network with an IP address Interval between two blinks 200 ms Gap 2 seconds Number of Blinks Cellular RSSI RSSI Range dBm 1 0 SNR 12 113 RSSI 89 2 12 SNR 21 89 RSSI 73 3 22 SNR 31 73 RSSI 51...

Страница 12: ...pecifications Cellular Specification Standards GSM GPRS EDGE UMTS HSPA LTE Band Options OnCell G3150A LTE EU B1 2100 MHz B3 1800 MHz B7 2600 MHz B8 900 MHz B20 800 MHz UMTS HSPA 2100 1900 850 800 900...

Страница 13: ...X 509 RSA GRE over IPsec Open VPN NAT T PFS DPD Management Options Remote SMS Control SNMPv1 v2c v3 Web Telnet Serial Console Others DDNS Software Specifications Moxa Proprietary GuaranLink Dual SIM...

Страница 14: ...ocated at least 20 cm away from the human body The OnCell G3150A LTE is NOT designed for the general public A well trained technician is required to deploy the OnCell G3150A LTE units and safely estab...

Страница 15: ...ndard so that it is accessible only by the use of a tool The device is not intended for use in an area with pollution degree rating 2 in accordance with EN 60664 1 When you install the OnCell G3150A L...

Страница 16: ...16 Grounding Wire Size The minimum cross sectional area of the grounding conductor should be equal to that of the input cable Moxa Inc No 1111 Heping Rd Bade Dist Taoyuan City 334004 Taiwan...