- 5 -
Wall-mount:
NOTE
The equipment is intended to be supplied by the external power
source (UL listed/ IEC 60950-1/ IEC 62368-1), which output
complies with ES1/SELV, PS2/LPS, output rating is 12 to 48
VDC, 0.455 A min., an ambient temperature 75°C minimum.
NOTE
Before connecting the Equipment to DC power inputs, make
sure DC power source voltage is stable
•
The wiring of input terminal block shall be installed by
skilled person.
•
Wire type: Cu
•
Only use 28-18 AWG wire size, torque value 0.5 N-m.
•
One individual conductor in a clamping point.
NOTE
If you are using a Class I adapter, the power cord should be
connected to an outlet with an earthing connection
Software Installation Information
You can download the User's Manual and Device Search Utility (DSU)
from Moxa's website: www.moxa.com. Please refer to the User’s
Manual for additional details on using the DSU.
The MGate 5119 also supports login via a web browser.
Default IP address:
192.168.127.254
Default account:
admin
Default password:
moxa