background image

 

- 7 - 

NOTE 

In the following section, ATEX and C1D2 certifications will be 
detailed separately. 

 

 

   

 

ATEX Information 

1.

 

DEMKO Certificate number: 17 ATEX 1848X 
IECEx Certificate number: IECEx UL 17.0019X 

2.

 

Ambient Temperature Range: 
0°C to 60°C (for models without suffix –T) 
-40°C to 75°C (for models with suffix –T only) 

3.

 

Certification String: Ex nA nC IIC T4 Gc 

4.

 

Standards Covered: EN 60079-0:2012+A11:2013/IEC 60079-0 6th 
Ed. AND EN 60079-15:2010/IEC 60079-15 4th Ed. 

5.

 

The conditions of safe use: 
a.

 

The equipment shall be installed in an enclosure that provides a 
degree of protection not less than IP 54 in accordance with 
IEC/EN 60079-15 and accessible only by the use of a tool. 

b.

 

Devices are for use in an area of not more than pollution 
degree 2 in accordance with IEC/EN 60664-1. 

c.

 

Provisions shall be made, either in the equipment or external to 
the equipment, to prevent the rated voltage from being 
exceeded by the transient disturbances of more than 140% of 
the peak-rated voltage. 

Installation instructions 

a. When wiring the relay contact (R), digital input (DI), and power 
inputs (P1/P2), we suggest using AWG (American Wire Gauge) 12-28 
(0.0804-3.31 mm²) as a cable and the corresponding pin-type cable 
terminals. The connector can withstand a maximum torque of 4.5 inch-
pounds.   
b. Conductors suitable for use in an ambient temperature of 85°C must 
be used for the power input terminal block.   
c. The cross-sectional area of the earthing conductors shall be at least 
3.31 mm² 

C1D2 Information 

1. These devices are open-type devices that are to be installed in an 
enclosure only accessible with the use of a tool and suitable for the 
environment. 
2. This equipment is suitable for use in Class I, Division 2, Groups A, B, 
C, and D or non-hazardous locations only.” 
 

 

WARNING 
EXPLOSION HAZARD 

Do not disconnect the equipment unless the power has been 
switched off, or the area is known to be nonhazardous. 

 

 

Содержание MGate 5118 Series

Страница 1: ...ericas Toll free 1 888 669 2872 Tel 1 714 528 6777 Fax 1 714 528 6778 Moxa China Shanghai office Toll free 800 820 5036 Tel 86 21 5258 9955 Fax 86 21 5258 5505 Moxa Europe Tel 49 89 3 70 03 99 0 Fax 49 89 3 70 03 99 99 Moxa Asia Pacific Tel 886 2 8919 1230 Fax 886 2 8919 1231 Moxa India Tel 91 80 4172 9088 Fax 91 80 4132 1045 2018 Moxa Inc All rights reserved ...

Страница 2: ...olor Description PWR 1 PWR 2 Green The power cable is connected Off The power cable is disconnected Ready Off Power is off or a fault condition exists Green Steady on Power is on and the unit is functioning normally Blinking The unit is responding to the software s Locate function Red Steady on Power is on and the unit is booting up Blinking Indicates an IP conflict or the DHCP or BOOTP server is ...

Страница 3: ...Flashing only A communication error occurred Master Mode 1 Received an exception code or framing error parity error checksum error 2 Command timeout the slave device is not responding Slave Mode 1 Received an invalid function code or framing error parity error checksum error 2 Accessed invalid register address or coil address Off No communication CAN Green Flashing only CANbus J1939 communication ...

Страница 4: ...tor SW CAN MODBUS 1 2 3 1 2 3 Pull high resistor Pull low resistor Terminator Pull high resistor Pull low resistor Terminator ON Reserved 120 Ω default 1 kΩ 1 kΩ 120 Ω OFF 150 kΩ default 150 kΩ default default Hardware Installation Procedure 1 Connect the power adapter Connect the 12 48 VDC power line or DIN rail power supply to the MGate 5118 s terminal block 2 Use a serial cable to connect the M...

Страница 5: ...bsite www moxa com Please refer to the User s Manual for additional details on using the Device Search Utility The MGate 5118 also supports login via a web browser Default IP address 192 168 127 254 Default account admin Default password moxa Pin Assignments Modbus Serial Port Male DB9 Pin RS 232 RS 422 RS 485 4W RS 485 2W 1 DCD TxD A 2 RXD TxD B 3 TXD RxD B Data B 4 DTR RxD A Data A 5 GND GND GND...

Страница 6: ...GND 4 TXD 5 RXD 6 DCD 7 CTS 8 DTR Power Input and Relay Output Pinouts V2 V2 V1 V1 Shielded Ground DC Power Input 2 DC Power Input 2 N O Common N C DC Power Input 1 DC Power Input 1 Specifications Power Requirements Power Input 12 to 48 VDC Power Consumption 416mA 12VDC 195mA 24VDC 110mA 48VDC Operating Temperature Standard model 0 to 60 C 32 to 140 F Wide temperature model 40 to 75 C 40 to 167 F ...

Страница 7: ... to the equipment to prevent the rated voltage from being exceeded by the transient disturbances of more than 140 of the peak rated voltage Installation instructions a When wiring the relay contact R digital input DI and power inputs P1 P2 we suggest using AWG American Wire Gauge 12 28 0 0804 3 31 mm as a cable and the corresponding pin type cable terminals The connector can withstand a maximum to...

Страница 8: ...RNING EXPLOTION HAZARD Indoor use and Pollution degree 2 WARNING EXPLOTION HAZARD The equipment and label must be wiped by a dry cloth WARNING EXPLOTION HAZARD This unit is intended to be supplied by an UL Listed IEC 60950 1 approved power supply suitable for use at 75 C And the power supply output meets SELV LPS and rated output 12 48 VDC and 416 mA minimum Moxa Inc Fl 4 No 135 Lane 235 Baoqiao R...

Отзывы: