background image

 

- 5 - 

and properly attach it to the DIN rail until it “snaps” into place. For 
wall mounting, install the wall-mount kit (optional) first and then 
screw the device onto the wall. The following figure illustrates the 
two mounting options: 

 

Software Installation Information 

You can download the User's Manual and DSU (Device Search Utility) 
from Moxa's website: www.moxa.com. Please refer to the User’s 
Manual for additional details on using the Device Search Utility. 
The MGate 5118 also supports login via a web browser. 
Default IP address: 

192.168.127.254

 

Default account: 

admin

 

Default password: 

moxa

 

Pin Assignments 

Modbus Serial Port (Male DB9) 

Pin  RS-232 

RS-422/ 

RS-485 (4W) 

RS-485 (2W) 

DCD 

TxD-(A) 

– 

RXD 

TxD+(B) 

– 

TXD 

RxD+(B) 

Data+(B) 

DTR 

RxD-(A) 

Data-(A) 

  5* 

GND 

GND 

GND 

DSR 

– 

– 

RTS 

– 

– 

CTS 

– 

– 

– 

– 

– 

 

 

*Signal ground 

CAN Port (6-pin Terminal Block) 

Pin  CAN 

CAN_L 

CAN_H 

CAN Signal GND 

Ext-CAN_L* 

Ext-CAN_H* 

CAN_SHLD 

 

 

Содержание MGate 5118 Series

Страница 1: ...ericas Toll free 1 888 669 2872 Tel 1 714 528 6777 Fax 1 714 528 6778 Moxa China Shanghai office Toll free 800 820 5036 Tel 86 21 5258 9955 Fax 86 21 5258 5505 Moxa Europe Tel 49 89 3 70 03 99 0 Fax 49 89 3 70 03 99 99 Moxa Asia Pacific Tel 886 2 8919 1230 Fax 886 2 8919 1231 Moxa India Tel 91 80 4172 9088 Fax 91 80 4132 1045 2018 Moxa Inc All rights reserved ...

Страница 2: ...olor Description PWR 1 PWR 2 Green The power cable is connected Off The power cable is disconnected Ready Off Power is off or a fault condition exists Green Steady on Power is on and the unit is functioning normally Blinking The unit is responding to the software s Locate function Red Steady on Power is on and the unit is booting up Blinking Indicates an IP conflict or the DHCP or BOOTP server is ...

Страница 3: ...Flashing only A communication error occurred Master Mode 1 Received an exception code or framing error parity error checksum error 2 Command timeout the slave device is not responding Slave Mode 1 Received an invalid function code or framing error parity error checksum error 2 Accessed invalid register address or coil address Off No communication CAN Green Flashing only CANbus J1939 communication ...

Страница 4: ...tor SW CAN MODBUS 1 2 3 1 2 3 Pull high resistor Pull low resistor Terminator Pull high resistor Pull low resistor Terminator ON Reserved 120 Ω default 1 kΩ 1 kΩ 120 Ω OFF 150 kΩ default 150 kΩ default default Hardware Installation Procedure 1 Connect the power adapter Connect the 12 48 VDC power line or DIN rail power supply to the MGate 5118 s terminal block 2 Use a serial cable to connect the M...

Страница 5: ...bsite www moxa com Please refer to the User s Manual for additional details on using the Device Search Utility The MGate 5118 also supports login via a web browser Default IP address 192 168 127 254 Default account admin Default password moxa Pin Assignments Modbus Serial Port Male DB9 Pin RS 232 RS 422 RS 485 4W RS 485 2W 1 DCD TxD A 2 RXD TxD B 3 TXD RxD B Data B 4 DTR RxD A Data A 5 GND GND GND...

Страница 6: ...GND 4 TXD 5 RXD 6 DCD 7 CTS 8 DTR Power Input and Relay Output Pinouts V2 V2 V1 V1 Shielded Ground DC Power Input 2 DC Power Input 2 N O Common N C DC Power Input 1 DC Power Input 1 Specifications Power Requirements Power Input 12 to 48 VDC Power Consumption 416mA 12VDC 195mA 24VDC 110mA 48VDC Operating Temperature Standard model 0 to 60 C 32 to 140 F Wide temperature model 40 to 75 C 40 to 167 F ...

Страница 7: ... to the equipment to prevent the rated voltage from being exceeded by the transient disturbances of more than 140 of the peak rated voltage Installation instructions a When wiring the relay contact R digital input DI and power inputs P1 P2 we suggest using AWG American Wire Gauge 12 28 0 0804 3 31 mm as a cable and the corresponding pin type cable terminals The connector can withstand a maximum to...

Страница 8: ...RNING EXPLOTION HAZARD Indoor use and Pollution degree 2 WARNING EXPLOTION HAZARD The equipment and label must be wiped by a dry cloth WARNING EXPLOTION HAZARD This unit is intended to be supplied by an UL Listed IEC 60950 1 approved power supply suitable for use at 75 C And the power supply output meets SELV LPS and rated output 12 48 VDC and 416 mA minimum Moxa Inc Fl 4 No 135 Lane 235 Baoqiao R...