background image

- 5 - 

Power Input and Relay Output Pinouts 

 

 

V2+ 

V2- 

 

V1+ 

V1- 

Shielded 

Ground 

DC 

Power 

Input 2 

DC 

Power 

Input 2 

N.O.  Common 

N.C. 

DC 

Power 

Input 1 

DC 

Power 

Input 1 

Specifications 

Power Input   

12 to 48 VDC 

Power Consumption 
(Input Rating) 

12 to 48 VDC, 430 mA (max.) 

Operating Temperature 

Standard Models: 0 to 60°C (32 to 140°F) 
Wide Temp. Models: -40 to 75°C (-40 to 
167°F) 

Storage Temperature 

-40 to 85°C (-40 to 185°F) 

ATEX and IECEx Information 

     

 

1.

 

DEMKO Certification number: 13 ATEX 1304499X 
IEC Certification Number: IECEx UL 13.0031X; 

2.

 

Ambient Temperature Range: 
0 to 60°C (for models without the -T suffix) 
-40 to 75°C (only for models with the -T suffix) 

3.

 

Certification String: Ex nA nC IIC T3 Gc 

4.

 

Standards Covered: EN 60079-0:2012+A11:2013;   
EN 60079-15:2010; IEC 60079-0 Ed.6; IEC 60079-15 Ed.4. 

5.

 

The conditions of safe usage: 
a.

 

The Ethernet Communications Devices are intended for mounting 
in a tool-accessible IP54 enclosure and used in an area of not 
more than pollution degree 2 as defined by IEC 60664-1. 

b.

 

Conductors suitable for use in an ambient temperature greater 
than 85°C must be used for the power supply terminal. 

c.

 

A 4 mm

2

 conductor must be used when a connection to the 

external grounding screw is utilized. 

d.

 

Provisions shall be made, either in the equipment or external to 
the equipment, to prevent the peak-rated voltage being 
exceeded by transient disturbances of more than 140%. 

Terminal Block (Plug mated with Socket): rated 300 V, 10 A, 105°C, 
12-28 AWG (0.0804 mm2 - 3.31 mm

2

) wire size, torque value 4.5 lb-in 

(0.509 N-m). The input terminal cable size 14 AWG ( 2.1 mm

2

 ). 

 

Отзывы: