- 5 -
Power Input and Relay Output Pinouts
V2+
V2-
V1+
V1-
Shielded
Ground
DC
Power
Input 2
DC
Power
Input 2
N.O. Common
N.C.
DC
Power
Input 1
DC
Power
Input 1
Specifications
Power Input
12 to 48 VDC
Power Consumption
(Input Rating)
12 to 48 VDC, 430 mA (max.)
Operating Temperature
Standard Models: 0 to 60°C (32 to 140°F)
Wide Temp. Models: -40 to 75°C (-40 to
167°F)
Storage Temperature
-40 to 85°C (-40 to 185°F)
ATEX and IECEx Information
1.
DEMKO Certification number: 13 ATEX 1304499X
IEC Certification Number: IECEx UL 13.0031X;
2.
Ambient Temperature Range:
0 to 60°C (for models without the -T suffix)
-40 to 75°C (only for models with the -T suffix)
3.
Certification String: Ex nA nC IIC T3 Gc
4.
Standards Covered: EN 60079-0:2012+A11:2013;
EN 60079-15:2010; IEC 60079-0 Ed.6; IEC 60079-15 Ed.4.
5.
The conditions of safe usage:
a.
The Ethernet Communications Devices are intended for mounting
in a tool-accessible IP54 enclosure and used in an area of not
more than pollution degree 2 as defined by IEC 60664-1.
b.
Conductors suitable for use in an ambient temperature greater
than 85°C must be used for the power supply terminal.
c.
A 4 mm
2
conductor must be used when a connection to the
external grounding screw is utilized.
d.
Provisions shall be made, either in the equipment or external to
the equipment, to prevent the peak-rated voltage being
exceeded by transient disturbances of more than 140%.
Terminal Block (Plug mated with Socket): rated 300 V, 10 A, 105°C,
12-28 AWG (0.0804 mm2 - 3.31 mm
2
) wire size, torque value 4.5 lb-in
(0.509 N-m). The input terminal cable size 14 AWG ( 2.1 mm
2
).