ioLogik R2110 Series User’s Manual
Introduction
1-4
Ground Connection
DIN-rail, and panel mount holes equipped ground connection
Terminal Block
Removable terminal block (3.81 mm) (DI/O)
Signal indication LEDs for each channel (DI/O)
Regulatory approval
Shock, free fall, vibration
CE Class A, Level 3, Criteria B
FCC Part 15, CISPR (EN55022) class A
UL 508 (pending)
Specific to the ioLogik R2110
The following specifications differentiate the ioLogik R2110 from other models in the R2000
series of ioLogik Remote I/O servers
I/O Type
12 DI, 8 DO
Digital Input
Dry contact
Logic 0: close to GND
Logic
1:
open
Wet contact
Logic 0: 0 to 3 VDC
Logic 1: 10 to 30 VDC
Low speed counter for limit switch with filtering (in 10 ms intervals)
Excess voltage protection (withstands voltage up to +36 VDC)
Source
Optical isolation 3K VDC
Pulse wave form settings in 10 ms
Excess voltage protection (withstands voltage up to +36 VDC)
Digital Output
Sink, 24 VDC, 200 mA
Optical isolation 3K VDC
Protection over temperature shutdown: Min, 170
°
C
Over voltage protection: 36 VDC
Over current limit: typ. 750 mA
LCD Display Module for Easy View Devices (Optional Accessory)
Text 16
×
2 LCM with backlight
Button
×
5 (up, down, right, left, center)
Hot pluggable to any ioLogik
Easy View
device
Unit ID, baudrate display, DI/O status display