ioLogik E1200 Series
Using the Web Console
3-6
For Event Counter mode, configure “Lo to Hi,” “Hi to Lo,” or “Both” to trigger the counter. The counter should
be set to either
start
, or
stop
. If it is in
stop
mode, the counter can be activated by the Modbus command.
Make sure that the Counter Filter is not set to 0; otherwise, the counter will never be activated.
The alias name and the logic definition can also be configured on this page.
DO Channels
On the DO Channels page, configure each DO (digital output) channel by clicking on the channel. DO Channels
can operate in DO mode or Pulse Output mode. In DO mode, output is either on or off. In Pulse Output mode,
configure the low width and high width to generate a square wave.
The
Power On Setting
field is used to specify the channel’s configuration when the ioLogik E1200 is powered
on, and the
Safe Status Setting
field specifies the channel’s configuration when the ioLogik E1200 enters Safe
Mode. Note that Safe Status is controlled by the Connection Watchdog, which is disabled by default. If the
Connection Watchdog is disabled, the ioLogik E1200 will never enter Safe Mode and your Safe Status settings
will have no effect.