ATEX and IECEx Information
1.
Certification number
DEMKO 09 ATEX0812123X
IECEx: IECEx UL 13.0046X
2.
Ambient range:
(-40°C ≤ T
amb
≤ 75°C)
3.
Certification string
ATEX: Ex nA nC IIC T4 Gc
IECEx: Ex nA nC IIC T4 Gc
4.
Standards covered:
EN 60079-0: 2012:+A11:2013/
IEC 60079-0:Ed 6.0
EN 60079-15: 2010/
IEC 60079-15:Ed 4.0
II 3G
DEMKO
09 ATEX 0812123X
Ex nA nC IIC T4 Gc
Ambient Range:
-40°C
≦
T
amb
≦
+75°C
Rated Cable Temp
≧
93°C
FI.4, No.135, Lane 235, Baoqiao
Rd. Xindian Diist., New Taipei City,
Taiwan
5.
Conditions of safe usage:
The Ethernet Communication Devices are only to be mounted in an
ATEX/ IECEx-certified tool-accessible IP54 enclosure and used in an
area of not more than pollution degree 2 as defined by IEC/EN
60664-1.
Provisions shall be made, either in the equipment or external to the
equipment, to provide the transient protection device to be set at a
level not exceeding 140% of the peak rated voltage.
6.
Additional use guide:
The conductor used for grounding is the same size as power
conductors. The temperature rating of input conductors shall be
higher than 92°C.The Terminal Block is suitable for 12-28 AWG
(3.31–0.08 mm²), torque value 4.5 lb-in.
Wiring Requirements
WARNING
Do not disconnect modules or wires unless the power has been
switched off or the area is known to be nonhazardous. The
devices may only be connected to the supply voltage shown on
the type plate.
These devices must be supplied by a SELV source as defined in
the Low Voltage Directive 2006/95/EC.
ATTENTION
This unit is a built-in type. It must comply with fire enclosure
stipulations of IEC60950-1/EN60950-1, or similar statements,
when installed in certain end equipment.