Charging the System with R-410A Refrigerant
Prepare the following items:
- Gauge manifold
- Vacuum pump
- R-410A refrigerant cylinder (Use a max of 90% of the initial weight)
- Scale
- Safety goggles
- Heavy-duty work gloves
WARNING
When handling refrigerant, the following precautions should always be observed. Failure to do
so may cause explosion, fire, loss of vision, lack of oxygen, burns, injury or unit malfunction.
• Refrigerant services must be performed by a licensed professional only
• Always wear proper eye protection and gloves while handling refrigerant
• Avoid working near flammable materials
• Work in well-ventilated area only
• Maintain the temperature of the refrigerant container below 104 °F (40 °C)
• Be careful not to allow refrigerant to contact eyes or skin
If liquid refrigerant strikes eye or skin:
• Do not rub the eye or skin
• Splash large quantities of cool water on the eye or skin
• Apply clean petroleum jelly to the skin
• Go immediately to a physician or hospital
Step 1
Step 5
Step 6
Step 4
Step 3
Step 2
Connect gauge manifold
1) Evacuate the system
• 15 minutes or more
• 30 inHg (100 kPa) or more of vacuum
2) Stop evacuating the system
• Leave for 5 minutes
3) Check the vacuum
Charge the system with R-410A
See “Technical Specifications” for the specified amount
Remove gauge manifold
Test the system for leaks
Connect to refrigerant source
If a leak is found,
repair the connection
or components.