Note:
The factory setting may diff er from the data shown in the table.
Note:
It is recommended not to change any setting marked with the word
NO
.
Connect the equipment to the mains (switch the circuit breaker on).
After switching the system on, press the key. In operation the display shows the temperature of water at the heat exchanger inlet and the heating
mode symbol.
Press the key to switch the heat pump off . The equipment will then stay in the standby state.
In the standby state the LED panel shows the actual time (if set).
In the operating state the LED panel displays the current water temperature.
Pressing the buttons and at the same time turns on the setting interface.
Use the buttons
to scroll through the list of parameters. Press the button to select the appropriate parameter (it will
flash on the display) and use the and buttons to set its value.
Press to confirm the setting and return to the next level.
To exit the mode, briefly press the button. If no button is pressed for approx. 20 seconds, the changes are automatically saved
and the display switches to the standard display.
5.2
HEAT PUMP SWITCHING ON AND OFF
5.3
OPERATIONAL PARAMETER SETTING AND CHECKING
No.
Meaning
Range
Setting (yes/no)
Factory setting
C0
Target temperature in the cooling mode
15 ~ 40 °C
yes
26 °C
C
1
Target temperature in the heating mode
1 ~ 10 °C
yes
1 °C
C
2
Target temperature in the automatic mode
7 ~ 40 °C
yes
1
C
3
Interval of checks of frosting
30 ~ 120 °C
yes
100 °C
C7
Defrosting start temperature
7~ 30 °C
yes
23 °C
C8
Defrosting stop temperature
1 ~ 10 °C
yes
1 °C
C12
Defrosting time
1 ~ 240 min.
yes
-7 °C
C13
Protection from low ambient temperature
-25 ~ 20 °C
yes
42 °C
C15
Temperature protection at compressor outlet
35 ~ 60 °C
yes
26 °C
H0
Automatic restart after power outage
0(no) 1(yes)
yes
45 min
H1
Ambient temperature (start of defrost mode)
0/1
NO
8 min
H2
Filtration pump mode
0/1
12 °C
H3
Adjustment of thermostat sensitivity (difference between
switch-out and switch-on temperatures)
1 ~ 25 °C
yes
-3 °C
H4
Temperature difference between evaporator inlet temperature
and ambient temperature (start of defrost mode)
-20 °C ~ 20 °C
H5
0 °C ~ 20 °C
P0
30 ~ 120 min
P1
0 °C ~ 15 °C
Adjustment of thermostat sensitivity (diff erence between
switch-out and switch-on temperatures)
Protection from high ambient temperature
Time interval of filter pump operation after compressor operation
1 ~ 25 min.
yes
yes
yes
yes
yes
5 °C
20 °C
15 min
0