3.

 

Operational parameters 

Please enter all of the subsequent parameters, as explained in section 

2

. 

 

3.1.

 

Input polarity 

 

 

 

 

InpoL 

 

 

 

nPn 

NPN: All inputs must switch to“0“ 

 

 

PnP 

PNP: All inputs must switch to “+“. 
For Namur: Set to NPN, see chapter 

4

. 

 

3.2.

 

Input filter  

 

 

 

 

Filter 

 

 

 

Off 

Filter off: Counting frequency up to 60 kHz 
see “Technical Specifications” (chapter 

6) 

 

 

 

on 

Filter on.  Maximum counting frequency 30 Hz 

 

3.3.

 

Input Mode of count impulses 

 

 

 

 

Input 

 

 

 

Cnt.dir 

Input A:  Count input  
Input B:  Direction select up/down 

 

 

 

Up .dn 

Differential: 
Input A: increments 
Input B: decrements 

 

 

 

 

Summing: 
Input A: increments 
Input B: increments 

 

 

 

Quad 

Quadrature up/down for signals A/B, 2 x 90° 
Counts rising edge of input A 

 

 

 

Quad 2 

Similar to “quad“, but with impulse doubling. 
Counts rising and falling edges of input A 

 

 

 

Quad 4 

Similar to “quad“, but with impulse quadrupling. 
Counts all edges of inputs A and B 

 

Содержание ZX020

Страница 1: ...Product Features Miniature panel housing Bright LED display with 6 digits Add on frame for clip or screw mounting Counting frequency 15 to 60 kHz depends on counting mode Selectable filter for use wi...

Страница 2: ...in other electronic and printed media as well as in the internet requires prior written authorization by motrona GmbH Table of Contents 1 Safety Instructions and Responsibility 3 1 1 General Safety I...

Страница 3: ...e right to modify the hardware software or operation manual at any time and without prior notice Therefore there might be minor differences between the unit and the descriptions in operation manual Th...

Страница 4: ...sections for wiring are described in the Technical Specifications see chapter 6 Before first start up it must be ensured that all connections and wires are firmly seated and secured in the screw term...

Страница 5: ...ed and additionally press the right one After releasing the keys the display alternates between the parameter title and the setting of the parameter After pressing any key only the parameter value for...

Страница 6: ...echnical Specifications chapter 6 on Filter on Maximum counting frequency 30 Hz 3 3 Input Mode of count impulses Input Cnt dir Input A Count input Input B Direction select up down Up dn Differential I...

Страница 7: ...by the divider set 99 9999 Setting range 0 0001 to 99 9999 Setting 0 will not be accepted 3 5 Decimal point dP 0 Sets the decimal point of the display 0 000 Max 3 decimal places 3 6 Set Reset mode re...

Страница 8: ...99999 Upon a Set Reset command the counter sets to the value entered here 99 9999 Range 199 999 999 999 3 8 End of program Endpro No Select No to return to the beginning of the menu for verification o...

Страница 9: ...Page 9 11 4 Terminal Assignments also printed to the top of the unit 5 Delivery includes Panel mounting clip Bezel for screw mounting with panel cut out 50 x 25 mm Bezel for clip mounting with panel c...

Страница 10: ...git height Range 6 digit LED red 8 mm 0 3149 inch 199999 999999 Housing Material Mounting Dimensions Miscellaneous Protection class Weight plastic panel cut out w x h 45 x 22 mm resp 1 772 x 0 866 inc...

Страница 11: ...0 157 6 5 0 256 59 0 2 323 22 x45 48 0 1 890 24 0 945 22 2 0 3 45 0 0 6 1 772 0 024 0 874 0 012 max 0 76 25 0 x 50 0 53 0 2 087 26 0 1 024 1 0 0 039 4 0 0 157 25 0 0 5 50 0 0 6 0 984 x 1 969 1 969 0...

Отзывы: