Parameter
Description
Serial Timer:
This register determines the cycle time in seconds for the cyclic
transmission. E. g. with a setting of 0.100 the selected register value will be
transmitted every 100 ms. The accuracy of the timer is +/-500 µs.
Setting the register to 0 disables cyclic transmissions.
Serial Value:
Selects the register to be transmitted cyclically.
Setting of 00 selects register code :0,
setting of 01 selects register code :1 etc.
The communication can operate in either “PC-Mode“ or in “Printer Mode“.
With “PC-Mode“, the unit waits for a request string and responds by a
corresponding data string.
For details of the protocol see description “SERPRO“.
With “Printer Mode“ the unit sends data without any request and under
Timer control. As soon as the unit receives a character, it automatically
switches to PC Mode and operates according to protocol. When for a
period of 20 sec. no character has been received, the unit switches
automatically to “Printer Mode“ and restarts cyclic data transmission.
Input Setting:
Input
Configuration
Sets the behavior of the Control input (terminal 10):
0 = static operation with “high” level
1 = dynamic operation by rising edge
2 = dynamic operation by falling edge
3 = dynamic operation by rising edge *)
4 =
dynamic operation by falling edge **)
5 =
static operation with “low” level
Input Function
Sets the function of the Control input (terminal 10):
0 = no function
1 = Set counter A to “Set Value A”
2 = Set counter B to “Set Value B”
3 = Set counter A to “Set Value A” and counter B to “Set Value B”
4 = Inhibit counter A (disable count)
5 = Inhibit counter B (disable count)
6 = Inhibit counters A and B
7 = Activate a serial data transmission cycle
*)
Equal to 1 (double command function for reasons of compatibility to the previous model)
**) Equal to 2 (double command function for reasons of compatibility to the previous model)